143
Operation Manual
FT1020G3 Rev 2.10.4
26.8
Setup wireless detectors (H5/A8)
This function can be used by commissioning / service engineer to set a Base station (4620)
for wireless units to one of the following modes:
Register:
in order to register one or more wireless detectors 4611 to the Base station
Unregister
: in order to unregister one or more wireless detectors 4611 from the Base
station
Install
: in order to change the normal communication time from every 2
nd
minute to every
5
th
second, to be used during commissioning, etc.
Note:
To set the Base station to any of the modes above, the Base station has to be in a
"Normal state" i.e. not set to any of the modes. For example, a Base station set to e.g.
"Register" mode has to be set back to "Normal state" before it can be set to any other
mode.
For more information, see the wireless technical manual.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H5.
H5 Service
"
↲
"
A1 Calibration of supervised output
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in Control Unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu A8
A8 Setup wireless detector
"
↲
"
Set base station mode
Set base station 000000 to one of the following:
Register
Unregister
Install
Write the technical number
for the Base station. Select
the required mode. Press
"
↲
". Base station in
Register mode is indicated
with "√" and a beep. It will
be shown in the Base
station mode list
E.g.:
“000001”
“Register”
Set base station mode
Set base station 000000 to Register
Unregister
√
Install
-- Base station mode (1) -------------------------------------------
Register, base station 000001
If the specified Base station
doesn't exist, it will be
indicated by "X" instead of
"√" and a beep.
Use the soft key "
|" to
toggle between "Set base
station mode" and the
"Base station mode" list.
Содержание Firetracker FT1020G3 CIE
Страница 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Страница 2: ...This page has deliberately been left blank...
Страница 174: ...174 Operation Manual FT1020G3 Rev 2 10 4 Figure 22 19 Rack 22U FT1020G3 General Arrangement with 6U battery box...
Страница 175: ...175 Operation Manual FT1020G3 Rev 2 10 4 Figure 23 19 Rack 13U FT1020G3 General Arrangement with 6U battery box...
Страница 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Страница 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...