111
Operation Manual
FT1020G3 Rev 2.10.4
After 15 minutes
or
"ESC" and
"Escape
menu"
Zone 001 in test mode
Zone 002 in test mode
Zone 003 in test mode
Zone 004 in test mode
(
Note:
See chapter "
", page 22 regarding priority order.)
You are logged out
but the zone(s) are
still in test mode.
"Menu"
Log in (see
above), select
menu H1,
step down to this view.
Zones in test mode:
001 002 003 004 End test:
↵
Press "
↵
" to end test.
"
↵
"
Please wait....
Test of routing equipment?
No
Yes
The LED "Test mode"
is turned OFF.
Press "
↵
" (i.e. select "No") to bypass the routing equipment test If so, the monthly test is
completed. The routing equipment test is always carried out from the ASE.
Monthly test is completed!
Press
↵
"
↵
"
▒▒▒
menu
H1 Perform monthly test
H2 .....
Scroll to another
menu or press
"ESC".
Note 1
: During the test, the following information will be shown in all other FDCIE displays:
Zone 001, 002, 003 or 004 in test mode
Note 2
: If an alarm point e.g. a manual call point is in alarm state when the test mode is
terminated, there will be a fire alarm activated.
Note 3
: When the "Fire door closing" function is used, the fire door will be closed when the
detectors controlling the door are tested, in test mode.
Содержание Firetracker FT1020G3 CIE
Страница 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Страница 2: ...This page has deliberately been left blank...
Страница 174: ...174 Operation Manual FT1020G3 Rev 2 10 4 Figure 22 19 Rack 22U FT1020G3 General Arrangement with 6U battery box...
Страница 175: ...175 Operation Manual FT1020G3 Rev 2 10 4 Figure 23 19 Rack 13U FT1020G3 General Arrangement with 6U battery box...
Страница 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Страница 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...