background image

Written by: JBJ 

Checked by: RP                                            Approved by   JBJ 

Document Number: Premier MX User 1.doc 

 Page 1 of 19 

14/12/06 

1

GLT Exports Limited 

Premier MX

 

Fire Detection/Alarm Panel and 

Premier MX

 

Repeater 

User Operation Manual

 

1.

 

List Of Contents 

1.  List Of Contents ........................................................................................................ 1 
2. Premier MX

 

User Operation - Fire and Fault Conditions ......................................... 3 

2.1.  If a fire is detected:............................................................................................. 3 
2.2.  To Silence the fire alarm sounders:.................................................................... 3 
2.3.  To Resound the fire alarm sounders after they have been silenced: .................. 3 
2.4.  To Reset the panel from a Fire Alarm:............................................................... 3 
2.5.  To operate the fire alarm sounders in Evacuate Mode:...................................... 4 
2.6.  If a fault is detected:........................................................................................... 4 
2.7.  To Silence the Buzzer: ....................................................................................... 4 

3. Premier MX

 

User Indications.................................................................................... 5 

3.1.  User Indications [showing optional Clock Module] .......................................... 5 
3.2.  User Controls - [showing optional Clock Module]............................................ 6 

4. Premier MX

 

User Controls – Disablement and Test Conditions. ............................. 7 

4.1.  To Disable/Enable any Zone or Zones............................................................... 7 
4.2.  To Disable/Enable all Sounders......................................................................... 7 
4.3.  To Disable/Enable the Fire Routing Output....................................................... 8 
4.4.  To Disable/Enable the Fault Routing Output..................................................... 8 
4.5.  To Disable/Enable Fire Protection Output[s]..................................................... 9 
4.6.  To Select/Clear One Man Zone Test................................................................ 10 
4.7.  To Select/Clear One Man Sounder Test........................................................... 10 
4.8.  To Enable/Disable Delay Mode ....................................................................... 11 
4.9.  To Override the Delay Mode ........................................................................... 12 
4.10. To Extend the Delay [from 1

st

 stage to 2

nd

 Stage] ........................................... 12 

4.11. Silencing the Alarms During the Delay: .......................................................... 12 
4.12. Resounding the Alarms after the Delay: [Alarms previously silenced]........... 12 

5.  User Operating Instructions for Optional Clock Module........................................ 12 

5.1.  To Display Alarm Event Count: ...................................................................... 12 
5.2.  To access the User Clock Module Edit Functions ........................................... 13 

6. Premier MX

  

Repeater Panel

 

User Operation - Fire and Fault Conditions.............. 15 

6.1.  If a fire is detected:........................................................................................... 15 
6.2.  To Silence the fire alarm sounders:.................................................................. 15 
6.3.  To Resound the fire alarm sounders after they have been silenced: ................ 15 
6.4.  To Reset the panel & repeater(s) from a Fire Alarm: ...................................... 15 
6.5.  To operate the fire alarm sounders in Evacuate Mode:.................................... 16 
6.6.  If a fault is detected:......................................................................................... 16 
6.7.  To Silence the Buzzer: ..................................................................................... 16 

Premier MX

 

Repeater Panel Operation [16 zone version shown] ............................... 17 

Содержание Premier MX-16

Страница 1: ...7 4 3 To Disable Enable the Fire Routing Output 8 4 4 To Disable Enable the Fault Routing Output 8 4 5 To Disable Enable Fire Protection Output s 9 4 6 To Select Clear One Man Zone Test 10 4 7 To Sel...

Страница 2: ...18 8 Routine Testing and maintenance 18 9 User responsibilities 18 10 Premier MX Isolate De isolate Test Mode Select Flowchart 19 Danger This equipment contains hazardous voltages that can cause deat...

Страница 3: ...output will operate after a delay if Fire Protection fault disabled LED is illuminated Locate the source of the fire alarm an LED will be visible on the detector which has been activated 2 2 To Silenc...

Страница 4: ...rm button to silence the fire alarm sounders and clear the Evacuate LED Set the Access Controls Keyswitch back to position 0 to lock the controls 2 6 If a fault is detected The panel buzzer will sound...

Страница 5: ...tput Steady when Fault Routing Output is disabled 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 0 1 C E L No 1800456 32 ZONE FIRE POWER SUPPLY ON POWER SUPPLY...

Страница 6: ...ed and if silence before reset is configured alarms silence switch has been operated 1 Press to stop the buzzer sounding in fire or fault conditions When controls are locked or unlocked Silence Buzzer...

Страница 7: ...o The zone fault disabled LED will change to the Off flash indication while the cursor is on it changing to off if the cursor is moved on o The general Disablement LED will be cleared if no other disa...

Страница 8: ...Fire Routing Output o Use the Select button to move the pulsed cursor indication up through the fault LEDs until it pulses the Fire Routing Fault Disabled LED The Select button moves the cursor down T...

Страница 9: ...lement LED will be cleared if no other disablements are present To quit the disable enable mode o To exit the Select Mode press the Select On Off button o The Select On LED will clear o The cursor ind...

Страница 10: ...rsor up To apply the test mode to the selected zone o Press the Test button to activate the test condition on the selected zone o The zone fault disabled LED will change to the On flash indication whi...

Страница 11: ...no other circuits are in the test condition To quit test selection mode o To exit the Select Mode press the Select On Off button o The Select On LED will clear o The cursor indication will clear o Se...

Страница 12: ...ill light The buzzer will silence The 2nd stage delay will start 4 11 Silencing the Alarms During the Delay Turn the Access Controls Keyswitch on the panel door to position 1 Press the Silence Alarms...

Страница 13: ...elect Access Control key switch to position 1 Press the SELECT ON OFF switch Use the Up down keys to scroll the cursor LED indication through the selectable options on the panel display LEDs until the...

Страница 14: ...et Display D N ON or D N OFF Change Change Pressing SELECT repeats the cursor display changes as above Pressing SELECT repeats the cursor display changes as above in reverse To exit Clock Module Menu...

Страница 15: ...put will operate after a delay if Fire Protection fault disabled LED is illuminated Locate the source of the fire alarm an LED will be visible on the detector which has been activated 6 2 To Silence t...

Страница 16: ...larm button to silence the fire alarm sounders and clear the Evacuate LED Set the Access Controls Keyswitch back to position 0 to lock the controls 6 6 If a fault is detected The repeater buzzer will...

Страница 17: ...tions Fault Yellow Flashes for a communications failure between the fire panel and repeater Sounder Fault Disabled Yellow Flashes for any sounder fault Steady for sounders disabled Sounder Test Yellow...

Страница 18: ...are locked or unlocked Silence Buzzer 2 In 2 Stage Delay Mode with stage 1 delay running press to start stage 2 delay otherwise all delayed outputs operate when Stage 1 timer times out When the panel...

Страница 19: ...button Precepten Panel Selected Circuit returned to normal operation LED pulses OFF flash Changes to OFF when cursor is removed Press DISABLE button Precepten Panel Selected Circuit Disabled Circuit...

Отзывы: