EYFR03 User Manual
33 of 110
v1.6.0
Chapter 3: Configuring the unit
20 January 2020
In standard mode, all parameters in the group must complete their batches before any parameter
can start a second batch. When a parameter completes, the tool used by that parameter will be
disabled. When the whole group is completed and
Lock on done
is set to No, all tools used by
parameters in the group will be enabled to run the group again.
Standard mode is intended for applications where multiple parameters must all be run the same
number of times. For example, a standard group could be used at a station with two operators
that need to attach the left and right brakes to a vehicle. In this case, each vehicle must have both
brakes attached, but there is no reason one must be attached before the other. However, each
vehicle should have both brakes attached before the next vehicle is started.
In free run mode, parameters in the group can run independently. When a parameter completes,
it restarts immediately and may perform additional tightenings. In this mode, the
Lock on done
and
Batch beep on
settings are ignored.
Free run mode is intended for applications where the qualifier simply needs to report the
tightenings from multiple tools but does not need to synchronize how much one tool runs
compared to another.
Group Parameter Selection
Figure 30: Group Parameter Select screen
Soft keys
1.
1-8 – Shows parameters slots 1-8 of the group
2.
9-16 – Shows parameter slots 9-16 of the group
3.
No function
4.
Exit [ESC] –Returns to the Group Edit screen
Changes made on this screen are saved or discarded when exiting the Group Edit screen.
Parameter column
In the parameter column, you may select the parameters for the group by typing the number of
the desired parameter in each row. The order on this screen determines the order they are shown
on the Run screen but is otherwise not important.
Batch column
In the batch column, you may enter the batch size for the parameter when running it as part of
the group. When a parameter is selected, this column will be filled with the batch currently
defined in the parameter itself. Changing values in this column only affect the parameter while it
Содержание EYFR03
Страница 1: ...EYFR03 User Manual v1 6 0 20 January 2020 ...
Страница 4: ...EYFR03 User Manual 4 of 110 v1 6 0 Quick Start 20 January 2020 Quick Start ...
Страница 8: ...EYFR03 User Manual 8 of 110 v1 6 0 Chapter 1 Overview 20 January 2020 Chapter 1 Overview ...
Страница 47: ...EYFR03 User Manual 47 of 110 v1 6 0 Chapter 4 20 January 2020 Chapter 4 Serial Communications ...
Страница 55: ...EYFR03 User Manual 55 of 110 v1 6 0 Chapter 5 Discrete I O 20 January 2020 Chapter 5 Discrete I O ...
Страница 58: ...EYFR03 User Manual 58 of 110 v1 6 0 Chapter 5 Discrete I O 20 January 2020 ...
Страница 74: ...EYFR03 User Manual 74 of 110 v1 6 0 Chapter 7 EtherNet IPTM 20 January 2020 Chapter 7 EtherNet IPTM ...
Страница 92: ...EYFR03 User Manual 92 of 110 v1 6 0 Chapter 7 EtherNet IPTM 20 January 2020 Total size 4 bytes ...
Страница 93: ...EYFR03 User Manual 93 of 110 v1 6 0 Chapter 8 ToolsNet 20 January 2020 Chapter 8 ToolsNet ...
Страница 100: ...EYFR03 User Manual 100 of 110 v1 6 0 20 January 2020 Chapter 10 PROFINET ...
Страница 104: ...EYFR03 User Manual 104 of 110 v1 6 0 Chapter 10 Data Management 20 January 2020 Chapter 10 Data Management ...
Страница 107: ...EYFR03 User Manual 107 of 110 v1 6 0 Chapter 11 Firmware Updates 20 January 2020 Chapter 11 Firmware Updates ...