16.4.7 H23 / H24 (Indoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty
connector
connection.
Faulty
sensor.
Faulty
PCB.
Troubleshooting
When abnormality indication starts again.
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Connector poor contact.
Correct the connection.
Defect in outdoor unit PCB.
Replace the outdoor unit PCB.
Defect in outdoor intake air temperature sensor.
Replace the outdoor air temperature sensor.
NO
NO
YES
YES
Check the connector connection:
Turn off the power.
Is the connector connection normal?
Check the connector connection.
Check the outdoor air temperature sensor:
Is the measured resistance of the outdoor air temperature
sensor matches the value specified in its characteristic
chart?
Plug out connector from the outdoor unit PCB.
Measure the resistance of the outdoor air temperature
sensor.
Caution
Sensor (Thermistor)
Characteristics
70
60
50
R
e
s
is
ta
n
ce
(k
Ω
)
40
30
20
10
0
1 Pipe temp. Sensor
2 Intake Air Temp. Sensor
1
2
14
(-10)
32
(0)
50
(10)
68
(20)
86
(30)
104
(40)
122
(50)
Temperature °F (°C)