13.14 Electric Heater Control 2
During Error happened, air conditioning unit will stop operation, TIMER LED will blink and indoor vane closed.
Electric heater can be switch ON when fullfill the starting condition as follow except 2 errors.
o
H14 (Indoor intake air temperature sensor abnormality)
o
H19 (Indoor fan motor mechanism lock)
Starting
condition
When all condition (1+2+3+4) are fulfilled.
o
Operation
ON
o
Indoor
Heating
mode
o
Error happened Except error H14 and H19
o
Temperature
different
control
Control
content
o
Indoor unit will start operate when receive operation ON signal from remote controller.
o
Indoor
fan
speed
For
error
Other
errors
minimum fan speed = Lo Fan
o
Once Electric heater switched ON, It will operate at least 3 minutes.
13.15 Base Pan Heater Control
Specification:
o
Power:
100
W
o
Voltage:
230
V
Purpose:
o
To control base pan heater cable operation to melt ice on base pan during heating operation
Starting
conditions:
o
When outdoor air temperature less than or same 5°C and A/C operation is heating
Control
contents:
o
Power supply to base pan heater is ON
Cancel
conditions:
o
When outdoor air temperature exceeds entry condition by 2°C after deice OR
o
When operation is not at heating mode
When air conditioning is
switched ON
Heater ON
Temp difference
(Remote controller setting -
Intake air temperature)
+2
+1
Heater OFF
ON by
Temp difference
≥
2.0deg
OFF by
Temp difference
≤
1.0deg
H23 - Indoor heat exchange sensor 1 abnormality
H24 - Indoor heat exchange sensor 2 abnormality
H27 - Outdoor air temperature sensor abnormality
H28 - Outdoor heat exchange sensor abnormality
Me Fan
(Fan speed higher than other error because the
outdoor unit compressor will still run at preset
frequency about 27Hz (H23, H24) and
40Hz (H27, H28)