Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Commissioning
8
►
Using the
[▼]
button, select the
Function
sub-menu and confirm with
[OK]
.
►
In the
Function
menu and using the
[▼]
button, select the area
Aquarea
► Confirm using the
[OK]
button.
►
Using the
[▼]
button in the
Aquarea
menu, select the
Settings
sub-menu.
► Confirm using the
[OK]
button.
The parameters in the sub-menu
Settings
are displayed and can be adjusted
as required.
The
Settings
sub-menu comprises the most important parametesr for the heat pump. The basic
settings are shown in the following table.
Some parameters were already automatically set by the selected system diagram (e.g. if a
domestic hot water tank is available or not,
Tank = 0
or
1
).
Name
Information text
Settings
Thermost
external room thermostat
0: no 1: yes
Tank
Domestic hot water tank
0: no 1: yes
BoosterH
Domestic hot water E-heating element
0: no 1: yes
AntiFr
Water frost protection function
0: no 1: yes
BoostDel
Time delay domestic hot water E-heating
element
Range: 20...95 min, Standard setpoint: 60 min
HeaterC
Output e-add heating interior unit
Range: 1, 2, 3, 6, 9 kW, Standard setpoint: 3 kW
Cooling
Cooling mode
0: no 1: yes
starting from
generation “F”
pumpRotRate
Pump rotation speed
Range: 0...7,
Standard setpoint: 4
starting from
generation “F”
DeviceHeat
Add.DH
0: no 1: yes
0: no, 1: de-icing,
2: outside < 5°C
starting from
generation “F”
BackupH-T
Backup heater to support heating up the
sanitary water tank
0: no, 1: yes;
Standard setpoint: 0
on All in One split heat
pump models
After adjusting the parameters, the supply voltage of the heat pump must be switched off to
establish the connection between the controller and heat pump using the adapter cable PAW-
HPMINT-x (appropriate to the heat pump type) The adapter cable is plugged in on the side of
the heat pumps in the respective circuit board plug for the control panel cable (→
Connections
of the Heat Pumps, P. 58
).
The other end of the adapter cable is connected to the BUS interface of the HPM controller
(→
Connection to the HPM controller during communication, P. 64
). Upon successful
connection, a beep will sound on the heat pump to confirm.
8.3.2 Heat source - strategy
On system diagrams with more than one heat pump, the demand-driven operation of the heat
pumps are controlled according to the settings in sub-menu
Strategy
. Via a control change,
the operating times can be evenly distributed over the heat pumps. This achieves a balance of
service life, maintenance intervals and signs of wear between the heat pumps.