8
additional heat source to support the heat pumps, after the last heat pump has been enabled by
the sequential switching. After assigning a relay output, the switch on and switch off delays for
the release and locking of the add. heat source can be set.
After the terminal assignment, the function is activated.
Name
Information text
Unit
St-SP Settings
addHS
Add. heat source
0 Assigning a relay output 1–13
swOnDel
Delayed switch-on
min
60 Switch-on delay after release of last heat
pump in the sequence
swOffDel
Delayed switch-off
min
0 Switch-off delay after locking of last heat
pump in the sequence
Domestic hot water Solar
This function is displayed, when a system diagram is loaded with the domestic hot water
circuit. The function controls the solar pump output, if the temperature difference between the
collector and tank is reached. After assigning an input terminal for the solar collector sensor, the
parameters listed below are displayed and can be adjusted as required.
If the function is used with a separate solar storage tank, then the input terminal of the
temperature sensor, which is installed in the solar storage tank, must be assigned as a solar
storage tank temperature (
solTank
). The relay output via which the pump is to be switched,
must be assigned as solar pump (
SolPu
). The parameters for the switching on and off, as well
as the safety functions (max. tank temperature, max. collector temperature (boil-out protection)
and min. collector temperature (frost protection) can be adapted to the system configuration.
The function is activated after assigning the input for the solar collector temperature and the
output for the solar pump.
Name
Information text
Unit
St-SP Settings
solColl
Solar collector temp.
0 Assigning a sensor input 17–24
solTank
Solar tank temp.
0 Assigning a sensor input 17–24
solPu
Solar pump
0 Assigning a relay output 1–13
TDiffSolOn
Temp. difference solar pump
on
K
8.0 Collector more than x,x K warmer as the
tank
TDiffSolOff
Temp. difference solar pump
off
K
2.0 Collector less than x,x K warmer as the tank
maxTSolTa
max. temperature Sol.-tank
sensor
°C
70.0 Solar pump locked, otherwise risk of burning
/scalding from the domestic hot water
maxTcoll
max. temperature collector
sensor
°C
110.0 Solar pump is switched on to prevent boiling
out
collFrLim
Frost.lim collector
°C
–10.0 Solar pump is switched on to prevent
freezing