Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Installation and Terminal Assignments
7
Fig. 7.18:
2
1
Heating only
4
3
H domestic hot
water
Individual heat pumps with control via contact release
1 HPM1:
SD No. 10xxx / 1 HP / Contact release
2 Heat pumps:
Terminals 17 + 18 / heating only
3 HPM1:
SD No. 17xxx / 1 HP / Contact release
4 Heat pumps:
Terminals 9 + 12 / H domestic hot water
Cascade – HP 1
On heating systems with more than one heat pump (cascade), the first heat pump (HP1) is
connected via terminals 9 and 12 with the “Room thermostat” function, if the heat pump is also
to generate domestic hot water. Otherwise it is connected to terminals 17 and 18
Heat pump 1 is used in this case primarily to control the domestic hot water tank: Loading times
of the tank, control of the 3-way valve and the feed flow set points depend on the settings that
the user entered on the control panel of the heat pump.
Therefore, the 3-way valve and the temperature sensor for the domestic hot water tank
must be connected to the heat pump
.
Cascade – HP2 and HP3
On heating systems with more than one heat pump (cascade) the second and third heat pumps
(HP2 and HP3) are connected via terminals 17 and 18 with the “External control signal/remote
switch” function.
These heat pumps are used in a cascade system exclusively for heating.