Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Technical Description
6
Application of the HPM models
The use of the two HPM models depends on the number of heat pumps in the heating system
and the control mode, as shown in the following table.
Number of heat pumps Control via contact release
Control via communication
1
1 x HPM1
1 x HPM1
2
1 x HPM1
1 x HPM1 (Master controller) and
1 x HPM2 (Slave controller)
3
1 x HPM1
1 x HPM1 (Master controller) and
2 x HPM2 (Slave controller)
6.3 Base
Layout of the base
The base of the HPM is a separate component. The base is divided into two areas by a partition
(
3
).
The left area contains extra-low voltage connections (
1
) e.g. for sensors and 0–10V signals; the
right area contains low voltage connections (
6
) (mains voltage 230 V) for valve actuators and
pumps (→
Terminal connection diagram on the inside of the controller, P. 48
).
Fig. 6.3:
1
4
5
6
3
2
Base with installed components
1 Terminals for low-voltage
2 Terminal distributor for sensor ground
3 Partition
4 Terminal distributor for PE (ground)
5 Terminal distributor for neutral line
6 Terminals for low-voltage
To prevent electromagnetic faults, terminal distributors are provided in both areas next to the
terminal strips: