72
Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Commissioning
8
Activating Easy setup
►
Using the
[▼]
button select the
easySetup
parameter.
easySetup = 1
: easy setup activated
The easy setup allows the most important parameters to be modified
(→
Parameters available for the easy setup, P. 73
). The available parameter
for the easy setup are shown directly under the
easySetup
parameter and can
be adjusted using the
[+]
and
[–]
button and confirmed with the
[OK]
button.
easySetup = 0
: Easy setup deactivated
The selected system diagram is loaded with the standard setpoints. The
parameters for the easy setup are hidden and can not be adjusted.
Performing cold start
Important notice
Using the parameter
cold start = 1
, the loading of the system diagram and the
currently set
parameter values
is started. All previous settings (if present) are lost. All parameter are set to
the values that were set at the time of the cold start.
►
Using the
[▼]
button, select the
cold start
parameter.
►
Using the
[+]
button, set the parameter to
1
and confirm with the
[OK]
button.
►
Watch the display until the following appears:
SYSTEM DIAGRAM XXXXX IS LOADED
.
The configuration of the controller is now completed.
The operating mode switches of the controller and the heat pumps must be set to
Off
after the
controller configuration. To put the system into operation, the operating mode switches must be
set to
Auto
(→
Operating Mode Switch, P. 39
).
If required, the parameter configuration can be changed after that. This allows for systems to
be integrated in the control, which were not previously considered by the per-configured system
diagrams.
The graphical representations of the WEB server integrated in the HPM are automatically
adjusted to the selected system diagram. The overview image of the heating system in the
WEBgrafic
view corresponds with the diagram selected in the m HPMtool.
Notice
After the HPM controller has been configured, the current configuration can be saved. For this,
the controller must be connected to a PC or Service Notebook and the correct software must be
used (e.g. hpm-read to read out, hpm-write to write back, hpm-control for menu operation via
PC).
!