SECTION 5
REMOTE OPERATION
82
5.3.2 TRANSIENT SEGMENT PARAMETERS
SEGment,<n>
selects transient segment n of the presently selected program to be
edited.
n
= <1> to <100>
FSEG,<n>
sets objective Frequency of selected segment.
n
= <:SOUR:FREQ:LIM:MIN> to <:SOUR:FREQ:LIM:MAX> Hz.
VSEG,<n>
sets
objective
voltage
Φ
A,
Φ
B,
Φ
C of selected segment.
n
= <0> to <150, or 150 x XFMRRATIO> Volts
VSEG1,<n>
sets
objective
voltage
Φ
A of selected segment.
n
= <0> to <150, or 150 x XFMRRATIO> Volts
VSEG2,<n>
sets
objective
voltage
Φ
B of selected segment.
n
= <0> to <150, or 150 x XFMRRATIO> Volts
VSEG3,<n>
sets
objective
voltage
Φ
C of selected segment.
n
= <0> to <150, or 150 x XFMRRATIO> Volts
WFSEG,<n>
sets
Waveform
Φ
A,
Φ
B,
Φ
C of selected segment.
n
= <1> to <16>
WFSEG1,<n>
sets
Waveform
Φ
A of selected segment.
n
= <1> to <16>
WFSEG2,<n>
sets
Waveform
Φ
B of selected segment.
n
= <1> to <16>
WFSEG3,<n>
sets
Waveform
Φ
C of selected segment.
n
= <1> to <16>
TSEG,<n>
sets execution time (to reach objective Voltage and Frequency) of
selected segment.
n
= <0> or <.0002> to <300> seconds. Setting n to <0> selects cycle-
based transient operation, i.e., each segment time is equal to the
period of 1 cycle (1/FREQ)
LAST
sets selected segment to be the last segment of selected transient.
Содержание UPC-12
Страница 2: ......
Страница 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK ...
Страница 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 32 Figure 1 3b UPC 32 Figure 1 3c UPC 12 ...
Страница 46: ...SECTION 4 OPERATION 34 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL ...
Страница 77: ...SECTION 4 OPERATION 65 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM ...
Страница 139: ...NOTES 127 NOTES ...
Страница 140: ...MODIFICATIONS 128 MODIFICATIONS MODIFICATIONS This section is reserved for any modifications that may be made ...