SECTION 6 CALIBRATION
84
6.3.2 POWER SOURCE LOAD TEST
This paragraph describes the test to be used to verify that the power source is able to deliver
rated load. Additionally, the output metering function of the controller is also checked.
The test proceeds in the manner below.
1.
Set the Power Source for 3
φ
Output (1
φ
for the Model 115-ASX, 2
φ
for Models 120-ASX
and 140-ASX), Direct-coupled, CSC Enabled.
2.
Attach a full-rated load to the
φ
A Output Terminal (1
φ
Output Terminal for the Model
115-ASX). (Refer to the list in paragraph 6.2 for the proper load.)
3.
Set the output for full-rated voltage and close the Output Contactor.
4.
Verify that the output voltage remains constant (within load regulation limits) and that the
Output metering reads correct values.
5.
Open the Output Contactor.
6.
Repeat
for
φ
B and
φ
C (
φ
B for 2
φ
and 3
φ
systems only,
φ
C for 3
φ
systems only) outputs.
7.
Configure for 1
φ
Output and repeat above procedure.
8.
If the system is outfitted with transformer outputs, set the Power Source for 3
φ
Output
(1
φ
for the Model 115-ASX, 2
φ
for Models 120-ASX and 140-ASX), Transform-
er-coupled, CSC Enabled.
9.
Verify that the output voltage and Power Source meters read properly.
Содержание ASX series
Страница 2: ......
Страница 8: ......
Страница 21: ...SECTION 2 SPECIFICATIONS 13 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 A MODEL 115 ASX OUTPUT DERATING CURVES ...
Страница 22: ...SECTION 2 SPECIFICATIONS 14 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 B MODEL 120 ASX OUTPUT DERATING CURVES ...
Страница 23: ...SECTION 2 SPECIFICATIONS 15 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 C MODEL 140 ASX OUTPUT DERATING CURVES ...
Страница 24: ...SECTION 2 SPECIFICATIONS 16 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 D MODEL 160 ASX OUTPUT DERATING CURVES ...
Страница 25: ...SECTION 2 SPECIFICATIONS 17 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 E MODEL 315 ASX OUTPUT DERATING CURVES ...
Страница 26: ...SECTION 2 SPECIFICATIONS 18 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 F MODEL 320 ASX OUTPUT DERATING CURVES ...
Страница 27: ...SECTION 2 SPECIFICATIONS 19 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 G MODEL 345 ASX OUTPUT DERATING CURVES ...
Страница 28: ...SECTION 2 SPECIFICATIONS 20 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 H MODEL 360 ASX OUTPUT DERATING CURVES ...
Страница 29: ...SECTION 2 SPECIFICATIONS 21 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 I MODEL 3120 ASX OUTPUT DERATING CURVES ...
Страница 69: ...SECTION 3 INSTALLATION 61 3 4 2 SPLIT PHASE OUTPUT cont FIGURE 3 4 2 1 SPLIT PHASE OUTPUT CONNECTION ...
Страница 70: ...SECTION 3 INSTALLATION 62 3 4 2 SPLIT PHASE OUTPUT cont FIGURE 3 4 2 2 SPLIT PHASE OUTPUT CONNECTION ...
Страница 72: ...SECTION 3 INSTALLATION 64 3 4 3 THREE PHASE OUTPUT cont FIGURE 3 4 3 1 THREE PHASE OUTPUT CONNECTION ...
Страница 73: ...SECTION 3 INSTALLATION 65 3 4 3 THREE PHASE OUTPUT cont FIGURE 3 4 3 2 THREE PHASE OUTPUT CONNECTION ...
Страница 76: ...SECTION 3 INSTALLATION 68 3 5 CONNECTION OF SYSTEM CONTROL UNIT SCU cont FIGURE 3 5 1 SCU CONNECTION ...