SECTION 2 SPECIFICATIONS
12
2.1.2 OUTPUT
POWER
OUTPUT VOLTAGE RANGE
DIRECT-COUPLED
The standard output voltage ranges of the ASX-Series are: 0-132 VAC
l-n
for the Models
115-ASX, 160-ASX, 315-ASX, and 360-ASX; 0-135 VAC
l-n
for the Models 140-ASX, 345-ASX,
and 3120-ASX; and 0-150 VAC
l-n
for the Models 120-ASX and 320-ASX, when operated in the
direct-coupled mode. These voltages are stated for nominal input voltage applied.
TRANSFORMER-COUPLED
The output voltage range of the ASX-Series Power Source varies when operated in the
transformer-coupled mode. Maximum output voltage is determined by the transformer turns
ratio. See list below for maximum output voltage vs. turns ratio.
TURNS RATIO MAXIMUM OUTPUT VOLTAGE (No Load)
1.5:1
198 VAC
l-n
Models 115-ASX, 160-ASX, 315-ASX, and 360-ASX
203 VAC
l-n
Models 140-ASX, 345-ASX, and 3120-ASX
2.0:1
264 VAC
l-n
Models 115-ASX, 160-ASX, 315-ASX, and 360-ASX
270 VAC
l-n
Models 140-ASX, 345-ASX, and 3120-ASX
2.5:1
330 VAC
l-n
Models 115-ASX, 160-ASX, 315-ASX, and 360-ASX
338 VAC
l-n
Models 140-ASX, 345-ASX, and 3120-ASX
OUTPUT CURRENT
FULL-RATED CURRENT
The full-rated output current the ASX-Series Power Source is listed below by model number.
Refer to the derating charts of Figures 2.1.2(A-H) for maximum output current at a specific output
form, voltage, or power factor. Output current ratings are scaled appropriately when using
transformer-coupled outputs. Note that the 315-ASX has reduced ratings when the output
magnetics option is installed (the "T" added to the model number designates the output
magnetics option). All other models retain their full-rated output current with the output
magnetics option installed.
1
φ
2
φ
3
φ
MODEL
I
out, rms
I
out, pk
I
out, rms
I
out, pk
I
out, rms
I
out, pk
115-ASX
16 A 35 A
N/A
N/A
N/A
N/A
120-ASX
20 A 90 A
14 A
45 A
N/A
N/A
140-ASX
32 A 90 A
16 A
45 A
N/A
N/A
160-ASX
48 A 120 A
16 A 45 A
N/A
N/A
315-ASX
12 A 69 A
6 A
23 A
4 A
23 A
315-ASXT
9 A
69 A
6 A
23 A
3 A
23 A
(with output magnetics option)
320-ASX
20 A 69 A
12 A
23 A
7 A
23 A
345-ASX
36 A 100 A
12 A
40 A
16 A
40 A
360-ASX
48 A 120 A
16 A
45 A
16 A
45 A
3120-ASX
96 A 300 A
48 A 150 A
32 A
100 A
OVERLOAD OPERATION
The ASX-Series Power Source will deliver up to 125% of rated RMS output current at 25
°
C
ambient room temperature, nominal through 10% high input line voltage, and at a power factor
of 0.8. Elevated ambient temperatures, low input line voltage, or power factors between 0.8 and
1.0 will increase the internal dissipation of the power source and can cause overload shutdown
due to over-temperature conditions. Length of time to reach over-temperature varies with the
models and the above parameters.
Содержание ASX series
Страница 2: ......
Страница 8: ......
Страница 21: ...SECTION 2 SPECIFICATIONS 13 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 A MODEL 115 ASX OUTPUT DERATING CURVES ...
Страница 22: ...SECTION 2 SPECIFICATIONS 14 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 B MODEL 120 ASX OUTPUT DERATING CURVES ...
Страница 23: ...SECTION 2 SPECIFICATIONS 15 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 C MODEL 140 ASX OUTPUT DERATING CURVES ...
Страница 24: ...SECTION 2 SPECIFICATIONS 16 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 D MODEL 160 ASX OUTPUT DERATING CURVES ...
Страница 25: ...SECTION 2 SPECIFICATIONS 17 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 E MODEL 315 ASX OUTPUT DERATING CURVES ...
Страница 26: ...SECTION 2 SPECIFICATIONS 18 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 F MODEL 320 ASX OUTPUT DERATING CURVES ...
Страница 27: ...SECTION 2 SPECIFICATIONS 19 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 G MODEL 345 ASX OUTPUT DERATING CURVES ...
Страница 28: ...SECTION 2 SPECIFICATIONS 20 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 H MODEL 360 ASX OUTPUT DERATING CURVES ...
Страница 29: ...SECTION 2 SPECIFICATIONS 21 2 1 2 OUTPUT POWER cont FIGURE 2 1 2 I MODEL 3120 ASX OUTPUT DERATING CURVES ...
Страница 69: ...SECTION 3 INSTALLATION 61 3 4 2 SPLIT PHASE OUTPUT cont FIGURE 3 4 2 1 SPLIT PHASE OUTPUT CONNECTION ...
Страница 70: ...SECTION 3 INSTALLATION 62 3 4 2 SPLIT PHASE OUTPUT cont FIGURE 3 4 2 2 SPLIT PHASE OUTPUT CONNECTION ...
Страница 72: ...SECTION 3 INSTALLATION 64 3 4 3 THREE PHASE OUTPUT cont FIGURE 3 4 3 1 THREE PHASE OUTPUT CONNECTION ...
Страница 73: ...SECTION 3 INSTALLATION 65 3 4 3 THREE PHASE OUTPUT cont FIGURE 3 4 3 2 THREE PHASE OUTPUT CONNECTION ...
Страница 76: ...SECTION 3 INSTALLATION 68 3 5 CONNECTION OF SYSTEM CONTROL UNIT SCU cont FIGURE 3 5 1 SCU CONNECTION ...