S-178-10(E)
(2) A list of Parameters
Parameter
Meter factor
Conversion
factor
Pulse weight
Indicated units
Instantaneous
flowrate
decimal point
Total flow
decimal point
Sampling time
Sample cycle
number
Pulse width
Symbol
F
H
Pu
Un
bP
SP
At
A
Pon
Default Setting
Depends on given specifications
(indicated on the parameter
label).
1.0000E0
Depends on given specifications
(indicated on the parameter
label).
L
0
0
5
(Note 3)
Depends on given specifications
(indicated on the parameter
label).
Depends on given specifications
(indicated on the parameter label).
Description
Meter factor of the flowmeter
(Unit: [L/pulse])
Conversion factor of units
(Unit: [Unit after convertion/L])
Weight of factored pulse
output
(Unit: [L/Pulse])
Unit-of-registration label
below LCD
Decimal point location,
Instantaneous flowrate (b1)
Decimal point location,
Accumulated total and resettable total
Upper limit of instantaneous
flowrate sampling time (Unit: [sec])
Frequency of sampling
"ON" duration of factored
pulse output (Unit: [msec])
Remarks
Example: Given meter factor 9.918mL/P
(=9.918
×
10
−
3[L/P])
→
Set to "F9.9180
−
3" (L/P).
To convert total flow and instant. flowrate units
to units other than L. (Normally H1.0000E0
unless unit conversion takes place.)
Example: at 1.5kg per 1L, to convert the
flowrate to read in kg
→
Conversion factor is 1.5 [kg/L] (=1.5000
×
1000[kg/L]; Set to "H1.5000E0" [kg/L]. (Note 1)
Example: To change factored pulse weight to
10L/P (=1.00
×
10
+1
[L/P]
→
Set to "Pu 1.00E1" (L/P). (Note 2)
By changing Un, units that appear on LCD
can be changed. (This is a change in
indicated units; it by no means influences flow
calculation.)
Example: To show instantaneous flowrate to
0.1 L/h (
=
one place below decimal point)
→
Set to "bP
.1".
Example: To show total flow to 0.01L (
=
two
places below decimal point)
→
Set to "SP .2".
If no flowrate pulse arrives during At [sec],
instantaneous flowrate is 0.
Instantaneous flowrate is determined by
timing the incoming flowrate pulses for A
times. If dispersion in instant. flowrate
indicated is too great, choosing a greater A
eases the problem.
Example: To obtain factored pulse width of
100ms
→
Set to "Pon 100" (ms). (Note 4)
NOTES: 1. If conversion factor (H) has been changed, pulse weight (Pu), indicated unit (Un) and other related factors need to be changed
relative to the modified unit of registration.
2. Set up such that
F
×
H
≦
Pu
≦
F
×
H
×
10000
without fail.
2
3. Default setting At = 9 only for meter size 49.
4. Be sure to set up a value such that factored pulse "OFF" duration > 1 ms.
5. Model without remote signal output (M\model suffix codex-400A) has parameters "Pu " and "Pon" set to 1.00E0 and 1, respectively.