Fault texts
35
negative draft does not
change
ڃ
Check negative draft tube for leaks. Check flue
gas tube for blockage.
Negative draft pressure
too low
ڃ
Close boiler door, check tube to negative draft
sensor,
check whether boiler flue gas outlet is clear,
check whether condensation heat exchanger is
clear.
Make sure flue gas fan is running.
Display:
Error code:
7
Description:
Safety temperature limiter has tripped
Cause and Remedy:
safety temperature limi-
ter unplugged
ڃ
connect up safety temperature limiter and check
cable connections
safety temperature limi-
ter has tripped
ڃ
check boiler controller
safety temperature limi-
ter defect
ڃ
allow boiler to cool and reset alarm
Display:
Error code:
8, 9
Description:
Flue gas minimum temperature not reached during ignition phase
Cause and Remedy:
no pellets available
ڃ
fill up with pellets
ignition electrode defect
ڃ
check ignition electrode (approx. 200
ˑ
) replace
if required
ignition nozzle blocked
ڃ
clean burner plate and ignition tube
flue gas sensor
contaminated
ڃ
clean flue gas sensor and flue gas tube
flue gas sensor is not in
flue gas tube
ڃ
insert flue gas sensor into flue gas tube
Display:
Error code:
10
Description:
Flame return gate open fault.
Cause and Remedy:
flame return gate
unplugged
ڃ
Connect up flame return gate and check cable
connections
Flame return gate does
not reach OPEN limit
switch
ڃ
check ball valve to see if it is jammed
no signal although open
ڃ
check cables and flame return gate
Error code:
11
Operating Manual Easypell® 16 — 32kW
Содержание Easypel
Страница 1: ...Operating Manual Easypell 16 32kW ENGLISH...
Страница 14: ...14 Emptying the ash pan 200013_EN 1 2...
Страница 16: ...16 Cleaning the boiler every year Procedure for cleaning the boiler 200013_EN 1 2...
Страница 18: ...18 Cleaning the boiler every year Cleaning the Induced draft blower 200013_EN 1 2...
Страница 38: ......
Страница 39: ......
Страница 40: ......