Malfunctions
33
110
0
Malfunctions
10.1 Malfunctions - what to do
Follow the sequence described for handling malfunctions.
• The heating system switches off automatically if a malfunction occurs.
• The control unit display shows a malfunction alarm text.
• You have to rectify the cause of the malfunction.
• After eliminating the underlying causes, you can restart the boiler.
10.2 Fault texts
The fault text displayed on the screen provides information on the type and status of the malfunction as well
as help for troubleshooting.
1.
Warning symbol
2.
Error code
3.
Error symbol
Note:
The system restarts automatically when the cause has been eliminated.
Overview of malfunction alarm texts:
Display:
Error code:
0
Description:
Boiler sensor fracture, measuring circuit from boiler sensor is open
Cause and Remedy:
sensor not connected
ڃ
connect sensor at input
sensor defect
ڃ
measure sensor (approx. 2k
ˑ
at 25° C) replace if
required
sensor cable defect
ڃ
replace sensor
sensor temperature too
high
ڃ
sensor temperature above measuring range
(1100° C)
Description:
Boiler sensor short circuit, measuring circuit from boiler sensor is shorted out
Cause and Remedy:
sensor defect
ڃ
measure sensor (approx. 2k
ˑ
at 25° C) replace if
required
sensor cable defect
ڃ
replace sensor
sensor temperature too
low
ڃ
sensor temperature below measuring range (-
10° C)
Operating Manual Easypell® 16 — 32kW
Содержание Easypel
Страница 1: ...Operating Manual Easypell 16 32kW ENGLISH...
Страница 14: ...14 Emptying the ash pan 200013_EN 1 2...
Страница 16: ...16 Cleaning the boiler every year Procedure for cleaning the boiler 200013_EN 1 2...
Страница 18: ...18 Cleaning the boiler every year Cleaning the Induced draft blower 200013_EN 1 2...
Страница 38: ......
Страница 39: ......
Страница 40: ......