USER MANUAL
OMX 103UNI
| 79
6.
MENU
PROFI
6.3.3c Setting the range of analoge output 1
2s
› › › OUT. ›
› › › A. O. ›
› A. 1 ›
› › › A.L.1 ›
A.L.1
Parameter
Display User
Setting
Description
Analogue output is isolated and its value
carresponds to the value on the display readout.
•
setting allows its two endpoints to be assigned
to any two points of the whole measuring
range (of display)
Beginning of
range of AO
A.L.1
-99
…
999
Assigning the display value to the beginning of
range of analoge output 1
•
Range: -99…999
•
DEF
0
→
→
End of range
of AO
A.H.1
-99
…
999
•
Assigning the display value to the end of range
of analoge output 1
•
Range: -99…999
•
DEF
100
→
→
A.L.1
i
Setting of analogue outputs
A. 2, A. 2
i
A. 3 is identical
to
the setting of output A. 1
6.3.4a Display backlight
2s
› › › OUT. ›
› › › › DIS. ›
› B. L. ›
B. L.
Parameter
Display User Description
Backlight
B. L.
Backlight setting
Off
NO
Backlight is off
On
YES
Backlight is on
On with timeout
TIM.
Backlight is time limited
DEF
•
It is activated by a key stroke for 60 seconds
•
It is activated automatically every time there is an error message
and it is accompanied by green LED flashing
→
→
B. L.