145
Programming Console Operations
Section 7-2
7-2-19 Unsigned Decimal Monitor
This operation is used to convert hexadecimal data in a word to unsigned dec-
imal for display. The operation can be executed while using I/O monitoring,
multiple address monitoring or 3-word monitoring.
1,2,3...
1.
Monitor the word that is to be used for decimal monitor without sign. During
multiple address monitoring, the leftmost word will be converted.
Multiple address monitoring
2.
Press the SHIFT+TR+NOT Keys to display the leftmost word as unsigned
decimal.
At this point, the contents of the displayed word can be changed with an
unsigned-decimal input. Refer to 7-2-25 Unsigned Decimal Data Modifica-
tion.
3.
Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal
display and return to normal monitoring.
7-2-20 Three-Word Data Modification
This operation is used to change the contents of one or more of the 3 consec-
utive words displayed in the Three-Word Monitor operation. It is possible in
MONITOR or PROGRAM mode only.
!Caution
Before changing the contents of I/O memory, be sure that the changes will not
cause equipment to operate unexpectedly or dangerously. In particular, take
care when changing the status of output bits. The PLC continues to refresh I/
O bits even if the PLC is in PROGRAM mode, so devices connected to output
points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1,2,3...
1.
Monitor the status of the desired words according to the procedure de-
scribed 7-2-17 Three-Word Monitor.
(Three-word monitor)
2.
Press the CHG Key to begin 3-word data modification. The cursor will ap-
pear next to the contents of the leftmost word.
3.
Input the new value for the leftmost word on the display and press the CHG
Key if more changes will be made.
(Input the new value and press the WRITE Key to write the changes in
memory if no more changes will be made.)
RUN
MONITOR
PROGRAM
OK
OK
OK
c200 cL0020000
FFF0 0000^ OFF
SHIFT
TR
NOT
c200
65520
CLR
c200 cL0020000
FFF0 0000^ OFF
RUN
MONITOR
PROGRAM
No
OK
OK
D0002D0001D0000
0123 4567 89AB
CHG
D0002 3CH CHG?
~
0123 4567 89AB
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание SYSMAC CPM2B
Страница 4: ...iv Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 6: ...vi Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 216: ...198 Index Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...