Application Procedure
Section 6-4
2.
Lay AC power supply lines and power lines separately.
3.
If noise interference from the power lines occurs, insert a noise filter in the
power supply and input section.
Preparing Analog I/O Cables
Analog I/O Boards are provided with two special I/O connectors. Always use
the provided connectors or equivalent products when wiring I/O.
Cable
Use shielded twisted-pair wires for the cables.
Wiring and Assembly
Use the following procedure to wire and assemble the connectors.
1,2,3...
1.
Pass the signal lines through heat-shrinking tube before soldering them to
each pin in the plug.
2.
After soldering all the required pins, return the heat-shrinkable tube on the
signal line to cover the solder joint, and shrink the tube using a hot air gun.
3.
Assemble the plug and hood, as shown in the following diagram. Use alu-
minum foil tape to wrap the folded back shield wire at the connector on the
Analog I/O Board, as shown in the diagram, and then fix to the hood.
Note After wiring the connectors, always check that all wiring is correct before turn-
ing ON the power supply.
Plug
XM2D1501
OMRON
Hood
XM2S1511
Soldering iron
Fold back the shield.
Heat-shrinkable tubing:
Hishi tube F
Internal dia.1.5, =10
1 mm
Heat-shrinkable tube
End connected to FG
Aluminum foil tape
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание SYSMAC CPM2B
Страница 4: ...iv Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 6: ...vi Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 216: ...198 Index Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...