Appendix D
Response Codes from the C200HX/HG/HE CPU
211
Main code
Remedy
Probable cause
Sub-
code
11: Parameter error
01
A correct memory area code has not
been used or Expansion Data Memory
is not available.
Check the command’s memory area code
and set the appropriate code.
02
The access size specified in the
command is wrong, or the first
address is an odd number.
Set the correct access size for the
command.
03
The first address is in an inaccessible
area.
Set a first address that is in an accessible
area.
04
The end of specified word range
exceeds the acceptable range.
Check the acceptable limits of the data
area and set the word range within the
limits.
Check the data link tables to be sure the
limit to link words has not been exceeded.
06
A non-existent program no. has been
specified.
Check the program number and be sure
that it is set correctly.
09
The sizes of data items in the
command block are wrong.
Check the command data and be sure that
the sixes of the data items are correct.
Check the data link tables to be sure all
nodes in the refresh parameters are in the
common link parameters.
0A
The IOM break function cannot be
executed because it is already being
executed.
Either abort the current IOM break function
processing, or wait until it is completed and
execute the command.
Check the data link tables for duplicate
node numbers.
0B
The response block is longer than the
max. permissible length.
Check the command format and set the
number of items correctly.
0C
An incorrect parameter code has been
specified.
Check the command data and reenter it
correctly.
Check the data link table file for corruption.
20: Read not possible
02
The data is protected.
Execute the instruction again after issuing
the PROGRAM AREA PROTECT CLEAR
command.
An attempt was made to download a
file that is being uploaded.
Check the file name and either interrupt
servicing or wait for servicing to complete
before re-executing the command.
03
The registered table does not exist or
is incorrect.
Set or reset the registered table.
Too many files open.
Close open files and re-execute the
command.
04
The corresponding search data does
not exist.
---
05
A non-existing program no. has been
specified.
Check the program number and be sure
that it is set correctly.
06
A non-existing file has been specified.
Check whether the correct file name was
used.
07
A verification error has occurred.
Check whether the memory contents are
correct and replace if incorrect.
Check the contents of the file. A read error
may have occurred.
Содержание SYSMAC C200HW-PCS01-EV1
Страница 1: ...Cat No W313 E1 3 PC Card Unit SYSMAC C200HW PCU01 C200HW PCS01 EV1 OPERATION MANUAL...
Страница 2: ......
Страница 3: ...SYSMAC C200HW PCU01 C200HW PCS01 EV1 PC Card Unit Operation Manual Revised January 2000...
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 12: ......
Страница 18: ......
Страница 34: ......
Страница 38: ......
Страница 60: ......
Страница 80: ......
Страница 82: ......
Страница 88: ......
Страница 120: ......
Страница 148: ......
Страница 178: ......
Страница 214: ......
Страница 220: ......
Страница 232: ......
Страница 234: ......
Страница 236: ......
Страница 238: ......
Страница 240: ......