131
9-6-4 Designating Remote Addresses
UDP sockets are used when sending FINS commands from a host computer to
the C200/HX/HG/HE. This subsection provides an example of addressing
remote PCs from the host computer for communications.
Host computer
IP address: 196.36.32.50
FINS network/node/unit: 1/32/0 hex)
Ethernet
PC Card Unit
Remote node
IP address: 196.36.32.100
FINS network/node/unit: 1/64/0 hex)
The communications parameters specified from the host computer would be as
follows:
Item
Setting
Remarks
Destination IP Address
196.36.32.100
PC Card Unit address
UDP port number
9600 (FINS UDP default port
number)
PC Card Unit’s UDP
port number
FINS addresses
DNA, DA1, DA2 = 1, 64, 0 (hex)
C200HX/HG/HE
SNA, SA1, SA2 = 1, 32, 0 (hex)
Host computer
FINS Communications From Computers
Section 9-6