30
Troubleshooting
Section 3-2
Indicators/Display
Error
Cause
ED Router
operation
Error
code
(hex)
Countermeasures
MS
NS D
NS E 7-seg-
ment
DeviceNet Communications-related Errors
---
Lit red ---
F0
Node
address
duplication
error
The ED Router
DeviceNet node
address is the
same as the
node address
set for another
device.
DeviceNet opera-
tion stops.
0211 Check the node addresses
and the network connections
for all devices on the
DeviceNet network.
---
Lit red ---
F1
Bus OFF
error
A DeviceNet bus
OFF error was
detected.
DeviceNet com-
munications stop.
0340 Check the DeviceNet net-
work for short-circuiting and
check the baud rate.
---
Not lit ---
E0
DeviceNet
network
power sup-
ply error
The DeviceNet
network power
supply is OFF.
DeviceNet com-
munications stop
until the network
power supply is
restored.
0341 Check the DeviceNet net-
work power supply and the
communications cable con-
nections.
---
Flash-
ing
red
---
E2
DeviceNet
communica-
tions timeout
error
Data could not
be sent in
DeviceNet for
1 s or longer.
DeviceNet com-
munications stop
until normal com-
munications are
restored.
0342 Check the following items:
• Is the baud rate the same
for each node?
• Are the cable lengths (main
and branch lines) correct?
• Are any cables discon-
nected or loose?
• Is terminating resistance
connected at both ends of
the main line?
Settings-related Error
Flash-
ing
red
---
---
F2
Ethernet
basic setting
error
An error
occurred in the
data set for the
TCP/IP Configu-
ration.
Operation contin-
ues, using the
default values for
the TCP/IP Con-
figuration.
03D0 Check the Ethernet settings.
Flash-
ing
red
Flash-
ing
red
---
C8
DeviceNet
node
address set-
ting changed
during oper-
ation
The node
address switch
setting was
changed during
operation.
Operation contin-
ues, using the
value from before
the change.
0214 Check the node address
switch setting. If the error
persists after the correct set-
ting has been made, replace
the ED Router.
Flash-
ing
red
---
Flash-
ing
red
C8
IP address
setting
changed dur-
ing operation
The IP address
switch setting
was changed
during operation.
Operation contin-
ues, using the
value from before
the change.
0214 Check the IP address switch
setting. If the error persists
after the correct setting has
been made, replace the ED
Router.
Flash-
ing
red
Flash-
ing
red
---
C8
Baud rate
setting
changed dur-
ing operation
The baud rate
switch setting
was changed
during operation.
Operation contin-
ues, using the
value from before
the change.
0214 Check the baud rate switch
setting. If the error persists
after the correct setting has
been made, replace the ED
Router.
Содержание NE1A-EDR01
Страница 1: ...OPERATION MANUAL Cat No Z912 E1 01 NE1A Series NE1A EDR01 EtherNet IP DeviceNet Router...
Страница 2: ...NE1A Series EtherNet IP DeviceNet Router NE1A EDR01 Operation Manual Produced July 2007...
Страница 3: ...iv...
Страница 7: ...viii TABLE OF CONTENTS...
Страница 9: ...x...
Страница 13: ...xiv...
Страница 41: ...24 ED Router Settings Section 2 5...
Страница 53: ...36 Error History Section 3 3...
Страница 97: ...80 DST1 Series Monitoring Section 4 7...
Страница 101: ...84 Settings from the Network Configurator Appendix B...
Страница 105: ...88 Glossary...
Страница 107: ...90 Revision History...