67
DST1 Series Monitoring
Section 4-7
Read Data Format (Read Size: 1 Byte)
Error Cause
(3) Instance ID
Status held in the DST1-ID12SL-1 can be monitored by reading the in-
stance IDs shown in the following table.
Data (status) indicated by a black dot (
●
) can be read.
I/O Assembly Data
Format
Instance ID: 20C
Monitor value: 1: ON, 0: OFF
Instance ID: 224
Monitor value: 1: ON, 0: OFF Status value: 1: Normal, 0: Error
+0
Error cause
Value
Meaning
0
No error
1
Illegal configuration
2
Test signal error
3
Internal circuit error
4
Discrepancy error
5
Error at dual channel partner
Instance
ID (hex)
Safety
input
Safety
input
batch
status
Safety
input
status
Safety
output
batch
status
Safety
output
status
Muting
lamp
status
Safety
output
monitor
Test
output
status
Overall
status
20C
●
224
●
●
22C
●
●
300
●
310
●
●
●
311
●
●
●
312
●
●
●
●
340
●
●
Offset
(bytes)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
+0
Safety input
terminal No.
7 monitor
Safety input
terminal No.
6 monitor
Safety input
terminal No.
5 monitor
Safety input
terminal No.
4 monitor
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
+1
Reserved
Safety input
terminal No.
11 monitor
Safety input
terminal No.
10 monitor
Safety input
terminal No.
9 monitor
Safety input
terminal No.
8 monitor
Offset
(bytes)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
+0
Safety input
terminal No.
7 monitor
Safety input
terminal No.
6 monitor
Safety input
terminal No.
5 monitor
Safety input
terminal No.
4 monitor
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
+1
Safety input
terminal No.
7 status
Safety input
terminal No.
6 status
Safety input
terminal No.
5 status
Safety input
terminal No.
4 status
Safety input
terminal No.
3 status
Safety input
terminal No.
2 status
Safety input
terminal No.
1 status
Safety input
terminal No.
0 status
Содержание NE1A-EDR01
Страница 1: ...OPERATION MANUAL Cat No Z912 E1 01 NE1A Series NE1A EDR01 EtherNet IP DeviceNet Router...
Страница 2: ...NE1A Series EtherNet IP DeviceNet Router NE1A EDR01 Operation Manual Produced July 2007...
Страница 3: ...iv...
Страница 7: ...viii TABLE OF CONTENTS...
Страница 9: ...x...
Страница 13: ...xiv...
Страница 41: ...24 ED Router Settings Section 2 5...
Страница 53: ...36 Error History Section 3 3...
Страница 97: ...80 DST1 Series Monitoring Section 4 7...
Страница 101: ...84 Settings from the Network Configurator Appendix B...
Страница 105: ...88 Glossary...
Страница 107: ...90 Revision History...