7. EtherNet/IP Connection Procedure
18
7. EtherNet/IP Connection Procedure
This section describes the procedures for connecting the code reader and controller on an
EtherNet/IP network.
In this document, it is assumed that the controller and the code reader use the factory default
settings. For how to initialize the devices, refer to
Section 8. Initializing the System
.
7.1. Operation Flow
The procedures for setting up the EtherNet/IP tag data links are as follows.
7.2. Code Reader Setup
▼
7.2.1. Setting the Parameters
7.3. Controller Setup
▼
7.3.1. Setting the IP Address
▼
7.3.2. Installing the EDS File
▼
7.3.3. Registering the Target Device
▼
7.3.4. Setting the Global Variables
▼
7.3.5. Registering the Tags
▼
7.3.6. Setting Up the Connections
▼
7.3.7. Transferring the Project Data
7.4. Checking the EtherNet/IP
Communications
▼
7.4.1. Checking the Connection Status
▼
7.4.2. Checking the Sent and
Received Data
Set up the code reader.
Set the parameters for the code reader.
Set up the controller.
Start the Sysmac Studio and set the IP address
of the controller.
Install the EDS file required for EtherNet/IP
communication with the code reader.
Register the target device.
Set the global variables to use for the tag data
links.
Register the tags and tag sets.
Set the target variables and the originator
variables to add connections, and then set up the
connections.
Place the Sysmac Studio online and transfer the
connection settings and project data to the
controller.
Check that the EtherNet/IP tag data links are
operating normally.
Check the EtherNet/IP connection status.
Check that the correct data is sent and received.