87
6
. Detailed settings for communications
6.3 CompoWay/F (continued)
Example of read parameter area communications
This example shows how to read two settings with one command where the phase and wire type is set to 1-phase 2-wire
and the communications address is 10
Command
Response
• If the phase and wire type is 1-phase 2-wire, H’00000000 is read. The communications address will be
H’0000000A=10 (decimal).
"(H’02)
10
00
0
02
01
C000
1000
8002
(H’03)
(H’49)”
STX
Commu
nication
address
Sub-
address
SID
MRC
SRC Parameter
Type
Start
reading
address
Number
of
element
s
ETX
BCC
"(H’02)
10
00
00
02
01
0000
1000
8002
STX
Commu
nication
address
Sub-
address
Exit
code
MRC
SRC Parameter
Type
Start
reading
address
Number
of
elements
00000000
0000000A
(H’03)
(H’08)"
Phase and wire
type
Communication
address
ETX
BCC