67
5.
Other Functions
5.9 Initialize (continued)
■
Resetting the active energy for all circuits
If a measured value is displayed, press and hold the [MODE• ] key and enter your password to switch to the setting
mode.
1
Press the [MODE• ] key to move to the other settings "ETC" category display screen.
2
From the other setting items, press the [
][
] keys to move to "All active energy reset (MENU 91)".
3
When you press and hold the [ENTER] key, the dashes (-) reduce from the left side of the main screen.
4
Keep pressing the [ENTER] key.
5
When the dash (-) disappears, and "DONE" flashes on the screen, the active energy for all circuits has
been reset.
After completing initialization, "MENU 91" is displayed again.
■
Resetting the active energy and setting values for all circuits
If a measured value is displayed, press and hold the [MODE• ] key and enter your password to switch to the setting
mode.
1
Press the [MODE• ] key to move to the other settings "ETC" category display screen.
2
From the other setting items, press the [
][
] keys to move to "Initialize (MENU 92)".
3
When you press and hold the [ENTER] key, the dashes (-) reduce from the left side of the main screen.
4
Keep pressing the [ENTER] key.
5
When the dash (-) disappears, and "DONE" flashes on the screen, the active energy and setting values for
all circuits has been reset.
After initializing, press and hold the [MODE• ] key to move to the measuring mode and restart the unit.
Information
• You can cancel the reset by pressing [ESC] before "DONE" is displayed.
1
2
4
5
3
Automatic transition
1
2
4
5
3
Automatic transition