25
2.
Installation and wiring
2.3 Wiring the power supply
Wire the input of the operational power supply with the power supply terminal.
The terminal layout of the power supply is as follows.
Recommended Ferrules
*1.
Make sure that the outer diameter of the wire coating is smaller than the inner diameter of the insulation sleeve of the
recommended ferrule.
Important
• For safety purposes, turn off the mains power and the breaker to ensure there is no power supply while
you are working.
• The terminal is the push-in type. Also read "Cautions when connecting the Push-In Plus terminal" when wiring.
• To wire with the power supply terminal, use AWG20-16 twisted or solid wire (with a cross-section of 0.5
to 1.5 mm
2
).
• Peel the wire-coating by 10 mm when using a ferrule terminal and by 8 mm when not using it.
• Use a ferrule terminal with a conductor portion 8mm long.
Applicable wire
Ferrule
conductor
length (mm)
Recommended ferrules
(mm
2
)
(AWG)
Manufactured by
Phoenix Contact
Manufactured by
Weidmuller
Manufactured by
Wago
0.25
24
8
AI0.25-8
H0.25/12
FE-0.25-8N-YE
0.34
22
8
AI0.34-8
H0.34/12
FE-0.34-8N-TQ
0.5
20
8
AI0.5-8
H0.5/14
FE-0.5-8N-WH
0.75
18
8
AI0.75-8
H0.75/14
FE-0.75-8N-GY
1
18
8
AI1-8
H1.0/14
FE-1.0-8N-RD
1.5
16
8
AI1.5-8
H1.5/14
FE-1.5-8N-BK
Recommended crimp tool
CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S
PZ6 roto
Variocrimp4
Power supply voltage
100 to 240 VAC
8 mm
Under2.1mm
Under 2.7mm
Terminal (Insertion) hole
Release hole
Wiring