8.3 Alarm/Warning Display and Troubleshooting
143
A.720
Overload:
Low load
Occurred when the
servo was turned
ON.
The servomotor wiring is
incorrect or connection is
faulty.
Correct the servomotor main
circuit cable wiring.
The encoder wiring is incor-
rect or connection is faulty.
Correct the encoder wiring.
The SERVOPACK is faulty.
• Replace the SERVOPACK.
• Contact your Omron
Yaskawa representative.
Occurred when the
servomotor did not
run by the refer-
ence input.
The servomotor wiring is
incorrect or connection is
faulty.
Correct the servomotor main
circuit cable wiring.
The encoder wiring is incor-
rect or connection is faulty.
Correct the encoder wiring.
The starting torque exceeds
the maximum torque.
Reconsider the load and oper-
ation conditions.
The SERVOPACK is faulty.
• Replace the SERVOPACK.
• Contact your Omron
Yaskawa representative.
Occurred while the
servomotor was
running.
The effective torque excee-
ds the rated torque, or the
starting torque largely
exceeds the rated torque.
Reconsider the load and oper-
ation conditions.
The SERVOPACK is faulty.
• Replace the SERVOPACK.
• Contact your Omron
Yaskawa representative.
A.730
Dynamic
Brake Over-
load
Occurred when the
servo was turns
OFF while the ser-
vomotor was run-
ning.
The servomotor did not stop
3 seconds or more after the
servo was turned OFF.
Reconsider the load and oper-
ation conditions.
Check if the servomotor is
rotated by external force.
(cont’d)
Alarm
Display
Alarm Name
Situation at Alarm
Occurrence
Cause
Corrective Actions