3 Communications Data for CompoWay/F
3 - 6
E5@D Digital Temperature Controllers Communications Manual (H225)
C1 (81)
003F
Work Bit 2 ON
Delay
H'00000000 to H'0000270F (0 to 9999)
Adjustment
C1 (81)
0040
Work Bit 2 OFF
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0041
Work Bit 3 ON
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0042
Work Bit 3 OFF
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0043
Work Bit 4 ON
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0044
Work Bit 4 OFF
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0045
Work Bit 5 ON
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0046
Work Bit 5 OFF
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0047
Work Bit 6 ON
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0048
Work Bit 6 OFF
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0049
Work Bit 7 ON
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
004A
Work Bit 7 OFF
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
004B
Work Bit 8 ON
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
004C
Work Bit 8 OFF
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0052
SP Response
Proportional Band
H'00000001 to H'0000270F (0.1 to 999.9)
C1 (81)
0053
SP Response
Integral Time
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
C1 (81)
0054
SP Response
Derivative Time
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
C1 (81)
0055
SP Response
Coefficient Number
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
0056
Disturbance
Proportional Band
H'00000001 to H'0000270F (0.1 to 999.9)
C1 (81)
0057
Disturbance
Integral Time
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
C1 (81)
0058
Disturbance
Derivative Time
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
C1 (81)
0059
Input Digital Filter
H'00000000 to H'0000270F (0.0 to 999.9)
C1 (81)
005A
Water-cooling
Output Adjustment
H'00000000 (0): OFF
H'00000001 (1): ON
C1 (81)
005B
Water-cooling
Proportional Band
Increase Threshold
Water-cooling Proportional Band Decrease Threshold
+ 0.1 to H'000007D0 (200.0)
Variable
type
Address
Parameter name
Setting (monitor) value
Level
Содержание E5 D Series
Страница 2: ......
Страница 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 108: ...5 Communications Data for Modbus 5 18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 200: ...6 Programless Communications 6 92 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Страница 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 209: ......