Note: The alarm function can also be used in Digital Temperature Controllers that do not have any auxiliary
outputs. In this case, confirm alarm occurrences via the status data.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C3 (83)
0020
Auxiliary Output 2
Open in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Advanced
function
setting
C3 (83)
0021
Alarm 2 Hysteresis H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial
setting
C3 (83)
0022
Auxiliary Output 3
Open in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Advanced
function
setting
C3 (83)
0023
Alarm 3 Hysteresis H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial
setting
C3 (83)
0024
HB ON/OFF
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
C3 (83)
0025
Heater Burnout
Latch
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0026
Heater Burnout
Hysteresis
H'00000001 to H'000001F4 (0.1 to 50.0)
C3 (83)
0028
α
H'00000000 to H'00000064 (0.00 to 1.00)
C3 (83)
002B
Input Digital Filter
H'00000000 to H'0000270F (0.0 to 999.9)
Adjustment
C3 (83)
002C
PV/SP No. 2
Display Selection
H'00000000 (0): Nothing displayed.
H'00000001 (1): PV/SP
H'00000002 (2): PV
H'00000003 (3): PV/SP (character display)
H'00000004 (4): PV/SP/MV (heating)
H'00000005 (5): PV/SP/Multi-SP No.
H'00000006 (6): PV/SP/Soak time remain
H'00000007 (7): PV/SP/Internal SP (ramp SP)
H'00000008 (8): PV/SP/Alarm value 1
H'00000009 (9): PV/SP/MV (cooling)
Advanced
function
setting
C3 (83)
002E
Automatic Display
Return Time
H'00000000 (0): OFF
H'00000001 to H'00000063 (1 to 99)
C3 (83)
002F
Alarm 1 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0030
Alarm 2 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0031
Alarm 3 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0032
Move to Protect
Level Time
H'00000001 to H'0000001E (1 to 30)
C3 (83)
0033
Integrated Alarm
Assignment
H'00000000 to H'0000007F (0 to 127)
C3 (83)
0034
Cold Junction
Compensation
Method
H'00000000 (0): OFF
H'00000001 (1): ON
Содержание E5 D Series
Страница 2: ......
Страница 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 108: ...5 Communications Data for Modbus 5 18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 200: ...6 Programless Communications 6 92 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Страница 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 209: ......