5 - 3
5 Communications Data for Modbus
E5@D Digital Temperature Controllers Communications Manual (H225)
5
-1 Variab
le Area (Set
tin
g Ran
g
e)
List
5
0426
2413
Power ON Time Monitor
H'00000000 to H'0000270F (0 to 9999)
Advanced
function
setting
0428
2414
Ambient Temperature
Monitor
When temperature unit is °C: H'FFFFFFE2 to H'0000004B (-30 to 75)
When temperature unit is °F: H'0000000A to H'000000AB (10 to 171)
0500
2500
Operation/Adjustment
Protect
H'00000000 (0):
No restrictions in operation and adjustment levels
H'00000001 (1):
Move to adjustment level is prohibited.
H'00000002 (2):
Display and change of only “PV” and “PV/SP”
parameters is allowed.
H'00000003 (3):
Display of only “PV” and “PV/SP” parameters is
allowed.
Protect
0502
2501
Initial
Setting/Communications
Protect
H'00000000 (0):
Move to initial setting/communications setting
level is allowed. (Move to advanced function
setting level is displayed.)
H'00000001 (1):
Move to initial setting/communications setting
level is allowed. (Move to advanced function
setting level is not displayed.)
H'00000002 (2):
Move to initial setting/communications setting
level is prohibited.
0504
2502
Setting Change Protect
H'00000000 (0): OFF (Changing of setup on controller display is
allowed.)
H'00000001 (1): ON (Changing of setup on controller display is
prohibited.)
0506
2503
PF Key Protect
H'00000000 (0): OFF
H'00000001 (1): ON
0508
2504
Move to Protect Level
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
050A
2505
Password to Move to
Protect Level
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
(Can only be set. The monitor value is always H’00000000.)
050C
2506
Parameter Mask Enable
H'00000000 (0): OFF
H'00000001 (1): ON
0600
2600
Manual MV
Standard control:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (
−
105.0 to 105.0)
Manual
control
0602
2601
Set Point
SP lower limit to SP upper limit
Operation
0608
2604
Heater Current 1 Value
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
060A
2605
MV Monitor (Heating)
Standard control:
H'FFFFFFCE to H'0000041A
(
−
5.0 to 105.0)
Heating and cooling control: H'00000000 to H'0000041A
(0.0 to 105.0)
060C
2606
MV Monitor (Cooling)
H'00000000 to H'0000041A (0.0 to 105.0)
0702
2701
Proportional Band
(Cooling)
H'00000001 to H'0000270F (0.1 to 999.9)
Adjustment
0704
2702
Integral Time (Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
0706
2703
Derivative Time (Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
0708
2704
Dead Band
H'FFFFF831 to H'0000270F
(
−
199.9 to 999.9 for temperature input)
(
−
19.99 to 99.99 for analog input)
070A
2705
Manual Reset Value
H'00000000 to H'000003E8 (0.0 to 100.0)
070C
2706
Hysteresis (Heating)
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
070E
2707
Hysteresis (Cooling)
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byt
e mode
Содержание E5 D Series
Страница 2: ......
Страница 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 108: ...5 Communications Data for Modbus 5 18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 200: ...6 Programless Communications 6 92 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Страница 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 209: ......