3 - 3
3 Communications Data for CompoWay/F
E5@D Digital Temperature Controllers Communications Manual (H225)
3-1 Variab
le Area (
S
et
tin
g
Ra
n
ge)
List
3
*2
When the variable type is 80 (word access), the rightmost 16 bits are read.
*3
When the variable type is 80 (word access), the leftmost 16 bits are read.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C1 (81)
0000
Operation/Adjustm
ent Protect
H'00000000 (0): No restrictions in operation and
adjustment levels
H'00000001 (1): Move to adjustment level is
prohibited.
H'00000002 (2): Display and change of only "PV"
and "PV/SP" parameters is allowed.
H'00000003 (3): Display of only "PV" and "PV/SP"
parameters is allowed.
Protect
C1 (81)
0001
Initial
Setting/Communic
ations Protect
H'00000000 (0): Move to initial
setting/communications setting
level is allowed. (Move to advanced
function setting level is displayed.)
H'00000001 (1): Move to initial
setting/communications setting
level is allowed. (Move to advanced
function setting level is not
displayed.)
H'00000002 (2): Move to initial
setting/communications setting
level is prohibited.
C1 (81)
0002
Setting Change
Protect
H'00000000 (0): OFF (Changing of setup on
Controller display is allowed.)
H'00000001 (1): ON (Changing of setup on
Controller display is prohibited.)
C1 (81)
0003
Set Point
SP lower limit to SP upper limit
Operation
C1 (81)
0004
Alarm Value 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0005
Alarm Value Upper
Limit 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0006
Alarm Value Lower
Limit 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0007
Alarm Value 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0008
Alarm Value Upper
Limit 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0009
Alarm Value Lower
Limit 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
000A
Alarm Value 3
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
000B
Alarm Value Upper
Limit 3
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
000C
Alarm Value Lower
Limit 3
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
000D
Heater Burnout
Detection 1
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
C1 (81)
000E
SP 0
SP lower limit to SP upper limit
C1 (81)
000F
SP 1
SP lower limit to SP upper limit
C1 (81)
0010
SP 2
SP lower limit to SP upper limit
C1 (81)
0011
SP 3
SP lower limit to SP upper limit
C1 (81)
0012
Process Value
Input Shift
H'FFFFF831 to H'0000270F (
−
199.9 to 999.9)
C1 (81)
0013
PV Input Slope
Coefficient
H'00000001 to H'0000270F (0.001 to 9.999)
C1 (81)
0015
Proportional Band
H'0000001 to H'0000270F (0.1 to 999.9)
Содержание E5 D Series
Страница 2: ......
Страница 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 108: ...5 Communications Data for Modbus 5 18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 200: ...6 Programless Communications 6 92 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Страница 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Страница 209: ......