6 Programless Communications
6 - 58
E5@D Digital Temperature Controllers Communications Manual (H225)
(2) We will change the communications settings for CH1.
Change the following settings, and then click the
OK
Button. Use the defaults settings for
the other parameters.
•
Parity Bit: Exist
•
Even/odd parity: Even
•
Stop bit: 2
•
Sum check code: Exist
•
Online Change: Enable
•
Setting modifications: Enable
•
Communication rate setting: 115,200 bps (This setting can be changed after you change
the communications protocol setting.)
•
Communication protocol setting: MC protocol (Format 4)
Note: If you change the station number setting, refer to
6-2-8 Communications Node Number
(3) Select
Online - Write to PLC
. A dialog box to write the set values will be displayed.