6 - 25
6 Programless Communications
E5@D Digital Temperature Controllers Communications Manual (H225)
6-4 C
onn
ectin
g t
o
CP-
series PLC
s
6
6-
4-3 PLC Setu
p
Communications Settings for the Serial Communications Option Board
(1) The PLC operating mode must be changed to PROGRAM mode to enable changing
the communications settings in the PLC Setup.
Select
PLC
−
Operating Mode
−
Program
from the menu bar. A confirmation dialog
box will be displayed. Click the Yes Button.
(2) Double-click Settings. The PLC Setup Window will be displayed.
(3) Click the Serial Option Port Tab, select the Custom Option, and set the baud rate to
115.2. Leave the other settings at their default values.
Note: If you change the unit number, refer to
6-2-8 Communications Node Number
.