Basic Examples of PID Control
Section
5-1
154
5-1-3
PID Control for Switching Multiple Set Points
Function blocks used: Basic PID (Block Model 011)
Contact Selector (Block Model 165)
DI Terminal from CPU Unit (Block Model 451)
Register multiple Set Points for switching in advance to the Constant Selector
block. Connect the DI Terminal from CPU Unit block to the Constant Selector
block, and switch the Local Set Points of the Basic PID block according to the
I/O memory (contacts) of the CPU Unit.
Use the Field I/O Terminal blocks (AI 4-point/AO 4-point Terminal blocks,
etc.) as the analog input/outputs.
PID
PV
MV
Set Point
switching
CPU Unit I/O’s
memory
MV
PV
Basic PID
Block Model 011
Analog input
Analog output
Contact Selector
Block Model 165
DI Terminal from
CPU Unit
Block Model 451
LSP
Contact switching
Contact
Distributor
Block Model 201
AI 4-point
Terminal
Block Model 586
AO 4-point
Terminal
Block Model 587