List of Operation Execution Times
Appendix 3
238
Sequence Command Execution Times
When the Step Ladder Program (Block Model 301) is used, add the following command execution
times to the operation execution time (3.39 ms) of the sequential control program itself.
Command code
Command
Execution time (ms)
Remarks
00
END
0.011
01
LOAD
0.137
02
LOAD NOT
0.137
03
AND
0.137
04
AND NOT
0.137
05
OR
0.137
06
OR NOT
0.137
07
AND LOAD
0.015
08
OR LOAD
0.015
11
OUT
0.104
12
OUT NOT
0.104
13
SET
0.104
14
RESET
0.104
15
DU
1.060
16
DD
1.060
21
STEP
0.011
22
BLOCK SET
0.990
23
BLOCK
RESET
1.827
25
JUMP
0.914
27
SETUP TIMER
0.014
The load rate increases by 0.01%
at an operation cycle of 100 ms.
28
ALARM TIMER
0.014
The load rate increases by 0.01%
at an operation cycle of 100 ms.
30
NOP
0.011