Basic Examples of PID Control
Section
5-1
160
5-1-7
Monitoring and Accumulating Flowrate
Function blocks used: PI 4-point Terminal (Block Model 562)
Accumulator for instantaneous value input (Block
Model 150)
Connect the instantaneous value output value of the PI 4-point Terminal
block to the Accumulator for instantaneous value input block when
accumulating 8-digit accumulated values based on the instantaneous values
from the Pulse Input Unit CS1W-PPS01.
Example
Let’s apply scaling of 0 to 6000 to zero (0%) through to span
(100%) of the pulsse input instantaneous value, and set
accumulation to maximum 1200.00 per hour. (The accumulated
value is taken to be 1200.00 when 6000 has continued for 100%
for one hour.) The accumulation result is stored to ITEM012 and
ITEM013 of the Accumulator for instantaneous value input block.
Accumulator for
instantaneous
value input
Block Model 150
Instantaneous
value
Pulse input
PI 4-point
Terminal
Block Model 562
Block address
ITEM No.
Data
Explanation
002
562
PI 4-point terminal block
010
3
Instantaneous value output range 3: 0 to 6000
901
021
0 to
115.00%
Y1 (instantaneous value output value 1) Note 1
002
150
Accumulator for instantaneous value input
007
901021
X1 source designation
008
Input
009
1200.00
QR accumulation rate (accumulation value when input
100% is continuous for one hour)
010
2
TU time unit (2: time)
012
0000 to
9999
Accumulated value (lower 4 digits)
100
013
0000 to
9999
Accumulated value (upper 4 digits)
Note 1
This instantaneous value differs from the instantaneous value, that is
reflected in the allocated relay words n+1 to n+4 of the Pulse Input Unit
CS1W-PPS01, in that the instantaneous value is for each operation cycle of
the PI 4-point Terminal block.