Specifications
Section
1-3
42
Item
Description
Basic
PID
Advan-
ced PID
MV high rate-of-
change limit
0 to 115.00%/s
Preset MV
switching
When the preset MV switch is set to ON, the MV
switches to the preset MV (fixed value) and control is
continued at this value.
MV hold
The MV (Manipulated Variable) is held at the current
value when the MV hold switch is ON.
MV tracking
The MV is switched (tracks) to the input value from other
blocks.
MV
compensation
Arithmetic operation (addition, subtraction, substitution)
is performed on the MV signals from the PID control
section when the MV compensation input switch is ON.
Out-of-range
processing at MV
output destination
block
PID accumulator is stopped when the range is exceeded
on the function block to which MV is connected.
MV
(Manipulated
Variable)
MV error input
MV error is transferred to CX-Process Monitor when the
MV error contact turns ON.
Alarm
PV alarm
4 (high/high limit, high limit, low limit, low/low limit),
setting range: each -15.00 to +115.00%
Hysteresis: 0 to +115.00%
Deviation alarm
1 (ON outside deviation)
State Output
1 current Set Point output (-15.00 to +115.00%),
1 deviation output (-115.00 to +115.00%)