![Omni OMNI-624 Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/omni/omni-624/omni-624_installation-and-setup-manual_4006703013.webp)
Section 2. System Wiring and Hookup
2-5
Furthermore, this device should not be connected to a phone line that has Call Waiting, unless the
Call Waiting Interrupt numbers are programmed into the panel dialing sequence.
BACKUP BATTERY:
The RED (+) and BLACK (–) flying leads must be connected to a 12VDC 4–7AH
lead acid battery, to serve as backup power in the event of AC loss.
A battery test occurs approximately every minute. Low-battery condition occurs at nominal 11VDC.
The keypad AC/LOW BAT LED and buzzer will pulse slowly when a low-battery condition is
detected. The system reports this condition to the CS if programmed to do so. There is also an
option that prevents the system from arming if a low battery has been detected (see Question 14,
L2). Battery restoral will occur within 4 minutes, at the next battery test. The buzzer may be
silenced by entry of any valid user code.
NOTE: For UL installations, use two 4AH batteries connected in parallel.
TRIGGER/RELAY OUTPUTS:
The control panel has four built-in programmable trigger outputs. In
addition, up to two XL4705 Relay Modules can be connected, providing 20 additional programmable
relay outputs. If the Relay Modules are used (enable modules in Programming Submode 1, Question
12, L2), then built-in triggers 3 and 4 are no longer used as trigger outputs, but serve as clock and
data inputs for the relay modules. See Programming Submode 1, Questions 32
–
43, for valid
trigger/relay types and programming.
NOTE: In order to connect devices to the triggers, use connector XL4612TC (trigger cable). Connect
to terminal P1 VBELL to obtain a POSITIVE reference point
.
Triggers 1, 2, 3, and 4 (3 and 4 when
not using XL4705) will go to a negative ground potential when active. For UL installations, the
trigger outputs shall be connected to devices rated to operate over the range from 10.1
–
14.0VDC at
50mA.
Auxiliary Device Current Draw Worksheet
DEVICE
CURRENT DRAW
FOR EACH
NUMBER
OF UNITS
TOTAL CURRENT
FOR ALL UNITS
Control Panel
65mA
1
65mA
OMNI-LCD (Backlight Off/On)
35mA/81mA
OMNI-KP
(Backlight Off/On)
28mA/45mA
XK-108L
42mA
PIR
**
Smoke Detector
**
Glassbreak Detector
**
**
**
TOTAL CURRENT FOR ALL DEVICES =
(500mA max.)***
** If the system is
using devices such as
PIR's, smoke
detectors, etc., refer to
the specifications for
that particular device's
current draw. If the
total current draw for
all devices exceeds
500mA, use an
additional power
supply.
*** For UL
installations, do not
exceed 180mA.
NFPA, UL, and the California State Fire Marshal require the backup battery to provide power
for 24 hours. The maximum aux. power will vary by the ampere/hour rating of the battery used:
5AH = 95mA; 7AH = 180mA; 8AH = 210mA.
Содержание OMNI-624
Страница 6: ...vi...
Страница 100: ...OMNI 624 OMNI 624EU Installation and Setup Guide 8 8...
Страница 102: ...OMNI 624 OMNI 624EU Installation and Setup Guide 9 2...