![Omicron CMC 356 Скачать руководство пользователя страница 58](http://html2.mh-extra.com/html/omicron/cmc-356/cmc-356_user-manual_3980661058.webp)
CMC 356 Reference Manual
58
6.4 Inputs
6.4.1 Binary
Inputs
Note:
If option ELT-1 is installed, only the general binary input data given in
the following Table 6-15 are valid. For detailed information about the option
ELT-1, please refer to section 6.10, "Option ELT-1" on page 67.
Table 6-15:
General data of
binary inputs
General Data of Binary Inputs 1…10
Number of binary inputs
10
Trigger criteria
Potential-free or DC-voltage compared to
threshold voltage
Reaction time
Max. 220 µs
Sampling frequency
10 kHz
Time resolution
100 µs
Max. measuring time
Unlimited
Debounce time
0…25 ms (refer to page 60)
Deglitch time
0…25 ms (refer to page 60)
Counting function
counter frequency
pulse width
3 kHz (per input)
>150 µs (for high and low signals)
Configuration
Binary inputs can be configured. Refer to the
OMICRON
Test Universe
Help.
Connection
4 mm/0.16 " banana sockets on the front
panel
Insulation
5 galvanic insulated binary groups with each
2 inputs having its own GND.
Operation insulation to the power outputs, DC
inputs and between galvanically separated
groups.
Reinforced insulation from all SELV
interfaces and from power supply.
Содержание CMC 356
Страница 1: ...CMC 356 User Manual...
Страница 38: ...CMC 356 Reference Manual 38...
Страница 100: ...CMC 356 Reference Manual 100...
Страница 104: ...CMC 356 Reference Manual 104...
Страница 132: ...CMC 356 Reference Manual 132...
Страница 136: ...The OMICRON Bootloader Software Copyright Notices 136...
Страница 138: ...Contact Information Technical Support 138...