10-7
Setpoints/Alarms
10
7.
“ALC.7=0”
ENABLES both Alarms 1 and 2 (Setpoints 3 and 4)
action and LEDs.
“ALC.7=1”
DISABLES both Alarms 1 and 2 (Setpoints 3 and 4)
action and LEDs.
8.
“ALC.8=0”
DISABLES Alarm reset at the P2-11 connector.
“ALC.8=1”
ENABLES Alarm reset at the P2-11 connector.
Press the
‘MENU’
button to store any changes and advance to “AL FNC”
(Alarm Function).
10.6 SELECTING “AL FNC” ALARM FUNCTION FEATURES
This byte allows you to select independent or ganged operation for “SP 3”
and “SP 4”, and whether or not they should latch once triggered.
1.
“ALF.1=0”
makes Alarm 1 (Setpoint 3) INDEPENDENT, with a level
equal to the value inserted for Setpoint 3.
“ALF.1=1”
assigns Setpoint 3 (“SP 3”) to Setpoint 1 (“SP 1”),
placing it ABOVE Setpoint 1 (“SP 1”) by the amount
entered for Setpoint 3 (“SP 3”).
“ALF.1=2”
places “SP 3” BELOW “SP 1” by the amount entered for
“SP 3”.
“ALF.1=3”
places “SP 3” ON BOTH SIDES OF “SP 1” by the
amount entered for “SP 3”.
2.
“ALF.2=0”
makes Alarm 1 (Setpoint 3) a NON-LATCHING Alarm.
“ALF.2=1”
makes Alarm 1 (Setpoint 3) LATCHING. This means
that once Alarm 1 (Setpoint 3) is triggered it will remain
active until it is reset by pressing the
‘RESET’
button
one time or by grounding P2-11 when configuration bit
“ALC.8=1” is set. Reset can also be accomplished via
the optional RS-232 or RS-485 serial communication
board.
3.
“ALF.3=0”
makes “SP 4” INDEPENDENT, with a level equal to the
value inserted for “SP 4”.
“ALF.3=1”
assigns “SP 4” to “SP 2”, placing it ABOVE “SP 2” by the
amount entered for “SP 4”.
“ALF.3=2”
places “SP 4” BELOW “SP 2” by the amount entered for
“SP 4”.
“ALF.3=3”
places “SP 4” ON BOTH SIDES OF “SP 2” by the
amount entered for “SP 4”.