9-5
Meter Function Menus
9
MENU
MIN/MAX*
BUTTON
BUTTON
MAIN MENU
SUB MENU
CONDITION
“L3 CNF”
“L3C.3=1”
AL CNF (mode of action of setpoints 3 & 4,
often used as alarms) cannot be locked
out.
“L3C.4=0”
AL FNC (Setpoints 3 & 4 independent or
ganged with Setpoints 1 and 2) can be
selected.
“L3C.4=1”
AL FNC (Setpoints 3 & 4 independent or
ganged with Setpoints 1 and 2) cannot be
accessed.
“L3C.5=0”
AL RDG (# of out-of-range readings before
trip of setpoints 3 & 4) can be selected.
“L3C.5=1”
AL RDG (# of out-of-range readings before
trip of setpoints 3 & 4) cannot be accessed.
“L3C.6=0”
SP DB (hysteresis or deadband of
Setpoints and Alarms) can be specified.
“L3C.6=1”
SP DB (hysteresis (deadband) of Setpoints
and Alarms) cannot be accessed.
“L3C.7=0”
OUT.CNF (analog & BCD outputs, setpoint
display flashing) can be specified.
“L3C.7=1”
OUT.CNF (analog & BCD outputs, setpoint
display flashing) cannot be accessed.
“L3C.8=0”
OT.SC.OF (2-data-point method for
independent analog-output scale/offset)
can be entered.
“L3C.8=1”
OT.SC.OF (2-data-point method for
independent analog-output scale/offset)
cannot be accessed.
* The
‘MIN’
button allows you to sequence through L3C.1, L3C.2, L3C.3,
L3C.4, L3C.5, L3C.6, L3C.7, and L3C.8.
The
‘MAX’
button allows you to select the “0” or “1” state for each “L3C”
condition.
The
‘MENU’
button stores the selected values for all “L3C” condition(s)
changed and advances the meter to “L4 CNF”. Do not press the
‘MENU’
button after each change within the submenu or the meter will advance to
the next menu item.
Every underlined “0” or “1” state is the factory preset value.