Pellematic settings
75
27.4 Run On Time settings
Run On Time
is in the Pellematic menu.
Run On Time has following menu items:
• Burner Fan Performance
• Flue Gas Fan Speed
• Burner Fan Run On Time
• Flue Gas Fan Run On Time
• Burner Fan/AGT Off
• Flue Gas Fan/AGT Off
• Burner Fan/FRT Off
• Flue Gas Fan/FRT Off
The additional menu items
Run On Time settings
are for the ÖkoFEN Service technician. They are present
after entering the code:
Burner Fan Performance
Adjusting the speed of the burner fan in the full power mode in percent. The speed
reduces continuously in the run on time.
Flue Gas Fan Speed
Adjusting the speed of the flue gas fan in the full power mode in percent. The speed
reduces continuously in the run on time.
Burner Fan Run On Time
Minimum run on time of the burner air fan at the moment of switch off in seconds.
Flue Gas Fan Run On Time
Minimum run on time of the flue gas fan at the moment of switch off in seconds
Burner Fan/AGT Off
The burner fan runs after the minimum delay time has elapsed even until the flue gas
temperature is lower than the boiler tempe the set temperature value:
e.g: Boiler temperature = 76°C + 32°C = 108°C Switch off temperature.
Flue Gas Fan/AGT Off
The flue gas fan runs after the minimum delay time until the flue gas temperature is
lower than the boiler tempe the set temperature value:
e.g: Boiler temperature = 76°C + 12°C = 88°C Switch off temperature.
Burner Fan/FRT Off
The burner fan runs after the minimum delay time until the combustion chamber
temperature is lower than the boiler tempe the set temperature value:
e.g: Boiler temperature = 76°C + 250°C = 326°C Switch off temperature.
Flue Gas Fan/FRT Off
The flue gas fan runs after the minimum delay time until the combustion chamber
temperature is lower than the boiler tempe the set temperature value:
e.g: Boiler temperature = 76°C +150°C = 226°C Switch off temperature.
E1389EN 2.0
Operating manual Pelletronic Touch