System Controlling
66
26
System Controlling
In the system menu you can adjust all heating system related parameters.
System Controlling
is in the Main menu.
Exisiting Boiler
In the menu item
Exisiting Boiler
are all parameters
to regulate the Pellematic with an existing boiler.
Cascade
In the menu item
Cascade
are all parameters for the
regulation of 2, 3 or 4 boilers.
Boiler Temp Above
Boiler Pump On Temp
If the Boiler temperature reaches the
Boiler Pump
On Temp
, the pumps are switched on.
Note
In heating systems with no accumulator, the
Boiler Pump On Temp
may lie not under
60°C.
Boiler Temperature Min
The
Boiler Temperature Min
protects the boiler.
In heating systems with no accumulator, the
Boiler
Temperature Min
may be not under 60°C.
Boiler Temperature Max
If the boiler or the accumulator reaches the
Boiler
Temperature Max
, all heating circuit pumps switch
on to transport the heat energy out of the boiler. This
process stops when the boiler temperature falls below
the
Boiler Temperature Max
–
Boiler Temp Above
.
(e.G.: BT Max 95°C minus Boiler Temp Above 10°C =
85°C)
Frost Protection – Protection Temp
If the outside temperature falls below the
Frost
Protection – Protection Temp
the heating circuits
are scavenged periodically. Default is 4°C, adjustable
from –20 to 4°C.
Note
The Frost Protection is additionally always
active: i.e. If the temperature of the
Flow
sensor
or the
AC upper sensor
is 8°C, the
burner demand activated.
Frost Protection– Scavenging Time/Pause Time
If the outside temperature falls below the
Frost
Protection – Protection Temp
the periodically
Scavenging occurs according to Scavenging Time
and Pause Time. Default values: Scavenging Time
5min and Pause Time 60 min.
Note
If the pump other reasons is activated
because of the Pause Time starts again.
Operating manual Pelletronic Touch
E1389EN 2.0