Heating circuits settings
55
21
Heating circuits settings
Heating circuits settings
is in the Main menu.
Heating circuits settings has following menu items:
• Mode
• Room Temp Heating
• Room Temp Set back
• Time Allocation
• Values
• Time 1
• Time 2
• Party
• Vacation
• Heating Curve
• Screed programme
See customer menu
7 Heating Circuit, page 16
The additional menu items
Heating circuits settings
are for the ÖkoFEN Service
technician. The icon setting appears in the menu Heating circuits only after the code
input. Touch the Icon
Setting
to reach all other adjustable parameters.
Max Flow temperature
Set the maximum flow temperature to the chosen heating circuit.
Min Flow temperature
Set the minimum flow temperature to the chosen heating circuit.
Temperature increase
(System heat loss
adjustment)
Set the boiler or accumulator temperature above the set flow temperature of the
circuit calling for the highest temperature.
E.g. Set at 5°C with a heating/DHW circuit with a set temperature of 60°C the
minimum boiler / accumulator temperature will be set to 65°C.
The boiler does not start when boiler/accumulator is above the minimum temperature.
Mixer Yes/No
Choose type of valve used to control heating circuits.
Heating circuit with mixer motor or direct heating circuit
Mixer open– rest – close
Is the opening / rest / closing time of the mixer.
Boiler load range
The mixer opening speed increases with boiler temperature in the set range.
E1389EN 2.0
Operating manual Pelletronic Touch