40 (48)
RE03 1406 EN
Performance
Performance presented is according to EN 14511:
● brine 0/35, performance without circulation pumps
● water temperature from the condenser: 35 ºC
● brine in temperature: 0 ºC.
RE 110
RE 140
RE 170
Heat from ground (kW)
78
101
125,2
Compressor power (kW)
29
36,5
43,2
Heating power (kW)
107
137,5
168,4
COP
3.6
3,8
3,9
Maximum condenser output
temperature (ºC)
(without desuperheater)
65
65
65
6.2. Condenser and evaporator circuit flow and pumps
Condenser and evaporator circuit flows
Condenser circuit flow
(Brine in 0 °C / water out 35 °C)
RE 110
RE 140
RE 170
Nominal flow rate, m
3
/h
18,5
23,8
29,2
Internal static pressure difference,
kPa
20
20
20
Pump electric power input required to
overcome the internal static pressure
difference (EN 14511-3), W
327
388
445
Evaporator circuit flow
(Brine in 0 °C / water out 35 °C)
RE 110
RE 140
RE 170
Nominal flow rate, m
3
/h
26,3
34,1
42,2
Internal static pressure difference,
kPa
30
30
30
Pump electric power input required to
overcome the internal static pressure
difference (EN 14511-3), W
547
652
755
Condenser pump, standard delivery
Condenser pump
RE 110
RE 140
RE 170
Manufacturer
Wilo
Wilo
Wilo
Type
IPL 50/115
- 0,75/2
IPL 50/115
- 0,75/2
IPL 50/115
- 0,75/2
Mains connection
3 x 400 V 50 Hz 3 x 400 V 50 Hz 3 x 400 V 50 Hz
Motor nominal (maximum) shaft
power (P2), W
750
750
750
Содержание RE 110
Страница 2: ......
Страница 45: ...RE03 1406 EN 43 48 WIPL02 ver 1 Figure1 Wilo IPL 50 115 0 75 2...
Страница 46: ...44 48 RE03 1406 EN WIPL01 ver 1 Figure2 Wilo IPL 50 120 1 5 2 and Wilo IPL 50 130 2 2 2...
Страница 47: ...RE03 1406 EN 45 48 WSP03 ver 1 Figure3 Wilo Stratos Para 25 1 7...
Страница 51: ......
Страница 52: ...www oilon com...