Wireless remote control (optional extra)
Operating line number
Function
120
Connection
121
Test mode
Heating circuit 1 / Heating circuit 2
Operating line number
(Heating circuit 1 / heating circuit
2)
Function
710 / 1010
Comfort setpoint
Set room temperature that heating circuit must
reach in comfort mode.
712 / 1012
Reduced setpoint
Set room temperature that heating circuit must
reach in reduced mode.
720 / 1020
Heating curve slope
See chapter
Configuring heating curve
.
721 / 1021
Heating curve displacement
If curve slope is suitable for heating circuit, but
room temperature is constantly too low or high
in comparison to set value, temperature can be
changed from operating lines.
‘+’ adjustment increases circulation setting and
room temperature
‘-’ adjustment decreases circulation setting and
room temperature.
730 / 1030
Summer/winter heating limit
Temperature when heating circulation is switched
on/off. Only operational in automatic mode.
740, 741 / 1040, 1041
Flow temp setpoint min, Flow temp setpoint max
Set maximum and minimum temperature for
heating circuit supply water temperature range.
This is a useful way for example to limit supply
water temperature sufficiently low at floor
heating locations. Floor heating circuit maximum
temperature should be limited to 40 °C. So called
floor drying function can be carried out by limiting
maximum temperature to 18 °C.
Domestic hot water
Operating line number
Function
1610
Nominal setpoint
Domestic hot water temperature setting at nominal
mode (sun).
Содержание RE 110
Страница 2: ......
Страница 45: ...RE03 1406 EN 43 48 WIPL02 ver 1 Figure1 Wilo IPL 50 115 0 75 2...
Страница 46: ...44 48 RE03 1406 EN WIPL01 ver 1 Figure2 Wilo IPL 50 120 1 5 2 and Wilo IPL 50 130 2 2 2...
Страница 47: ...RE03 1406 EN 45 48 WSP03 ver 1 Figure3 Wilo Stratos Para 25 1 7...
Страница 51: ......
Страница 52: ...www oilon com...