5. Maintenance
5.1. Annual maintenance
Heat pumps containing more than 3000 g of refrigerant must be annually checked and
maintained by a professional service provider.
Annual maintenance includes cleaning, and if necessary replacing, the circuit filters. In
addition, all circulation pumps, actuators and sensors are checked.
Each time an annual maintenance is performed, the service provider must fill a form
in the maintenance sheets (delivered with the heat pump), as well as add a sticker
informing about the next required annual maintenance. The sticker should be located in
a visible place of the heat pump.
5.2. Cleaning the brine circuit filter
Switch off electricity before performing any maintenance work.
Open the filter carefully, as there is fluid in the pipe.
1. Switch off the heat pump using the main power switch
Q1
.
2. Shut the filter isolation valves.
3. Open the filter cover.
4. Remove the filter element and clean it by rinsing with water.
5. Place the filter element back.
6. Fill the filter space with brine.
7. Close the filter cover.
8. Open the filter isolation valves.
9. Switch the heat pump back on using the main power switch
Q1
.
5.3. Troubleshooting
Failure codes
Device failures are displayed on the control panel. Check the failure code and cause by
pressing
Information
button.
No. Definition
Sensor Cause
Action
10
Outside sensor
BX9
No outside sensor
Check outside sensor
connection.
30
Flow sensor 1
BX11
No measurement
from outgoing water
Check Heating Circuit 1
flow sensor connection.
Содержание RE 110
Страница 2: ......
Страница 45: ...RE03 1406 EN 43 48 WIPL02 ver 1 Figure1 Wilo IPL 50 115 0 75 2...
Страница 46: ...44 48 RE03 1406 EN WIPL01 ver 1 Figure2 Wilo IPL 50 120 1 5 2 and Wilo IPL 50 130 2 2 2...
Страница 47: ...RE03 1406 EN 45 48 WSP03 ver 1 Figure3 Wilo Stratos Para 25 1 7...
Страница 51: ......
Страница 52: ...www oilon com...