42 (48)
RE03 1406 EN
Pressure differential at nominal
flow rate, kPa
120
143
124
Total head available to
overcome the external pressure
losses, m
9,5
11,9
9,9
Pressure differential available to
overcome the external pressure
losses, kPa
90
113
94
Desuperheater pump, standard delivery
Desuperheater pump
RE 110
RE 140
RE 170
Manufacturer
Wilo
Wilo
Wilo
Type
Stratos
Para 25/1–7
Stratos
Para 25/1–7
Stratos
Para 25/1–7
Mains connection
1 x 230 50 Hz
1 x 230 50 Hz
1 x 230 50 Hz
Motor nominal (maximum) shaft
power (P2), W
50
50
50
Motor nominal (maximum)
electric current, A
0,58
0,58
0,58
Thread size / Nominal flange
diameter
G 1 1/2
G 1 1/2
G 1 1/2
Overall lenght, mm
130
130
130
Weight, kg
2,2
2,2
2,2
Minimum required suction head
(NPSHR), m
3,0
3,0
3
Minimum required suction
pressure, bar
0,3
0,3
0,3
Pump curves
The pump curves of the different pump types are illustrated in the following.